Troubleshooting
31
5.0
T
ROUBLESHOOTING
Table 23
Troubleshooting
Problem
 Cause
 Remedy
Unit will not start
No power to unit
Check voltage at input terminal block.
Compressor contactor not pulling in
Check for 24VAC ±2VAC at control connections 1 & 2. If 
no voltage, check control setting requires cooling. If there 
is voltage, lockout relay may be energized. Check for 
24VAC at control connections 2 & 3. If there is voltage, 
see compressor high-discharge pressure/lockout relay.
Control voltage circuit breaker (at 
transformer in evaporator module) 
open
Locate short and reset circuit breaker.
Short cycle prevention control
Control software delays compressor 3 minutes from stop 
to start.
Compressor high discharge 
pressure/ lockout relay
Check for 24VAC ±2VAC at control connections 2 & 3. 
Remove 24VAC signal at Connection 2 by turning indoor 
unit control off, then back on, or by raising the setpoint to 
remove the cab for cooling, then resetting to re-establish 
operation.
High discharge 
pressure
Insufficient air flow across 
condenser coil
Check fan operation. Remove debris from coil and air 
inlets.
High refrigerant charge
Check refrigerant charge.
Low discharge pressure
Faulty head pressure control valve
Replace if defective.
Compressor rotation in reverse 
direction
Check for proper power phase wiring to unit and to 
compressor motor.
Low suction pressure / 
compressor cycling
Insufficient refrigerant in system
Check for leaks; repair and add refrigerant.
Plugged filter drier
Replace filter drier.
Improper superheat adjustment
Reset expansion valve for 10-15°F (5.6 to 8.4°C) 
superheat at evaporator.
Defective liquid line solenoid valve
Check valve and coil; replace if necessary.
Low compressor 
capacity/ no cooling
Defective liquid line solenoid valve
Check valve and coil; replace if necessary.
Plugged filter drier
Check pressure drop across filter drier. Replace filter 
drier.
Low refrigerant charge
Check for normal system operating pressures. Refer to 
abnormal pressure causes if applicable. Check for leaks. 
Proper refrigerant charge is very important at low ambient 
operation.
Compressor noisy
Loose compressor or piping 
support
Tighten clamps.
Compressor rotation in reverse 
direction
Check for proper power phase wiring to unit and to 
compressor motor.
Pipe Rattle
Loose pipe connections
Check pipe connections.
Compressor running hot
Compression ratio too high
Check for normal system operating pressures. Refer to 
abnormal pressure causes if applicable.
Compressor motor 
protectors tripping or 
cycling
High discharge pressure
Check for blocked condenser fan or coil.
High suction temperature
Check expansion valve and hot gas bypass valve setting. 
Check liquid quenching valve operation.
Loose power or control circuit 
wiring connection
Check all power and control circuit connections.
Defective motor
Check for motor ground or short. Replace compressor if 
either condition is found.
Compressor cycles on 
locked rotor
Low line voltage
Check line voltage and determine location of voltage drop.
Compressor motor defective
Check for motor winding short or ground.
Single phasing
Check voltage across all 3 legs at contactor. Correct 
source of problem.
Motor burnout
Check control panel for welded 
contactor contacts or welded 
overload contacts.
Replace defective components.