Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the 
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
H1RA030S78A
INDOOR COIL MODEL NO.
G2FD030S17
CONDENSER
ENTERING AIR
TEMPERATURE
IDCFM
650
850
1050
ID DB (°F)
85
80
70
85
80
70
85
80
70
ID WB (°F)
72
67
57
72
67
57
72
67
57
75
T.C.
26.4
25.3
24.0
26.6
25.7
24.6
26.7
26.1
25.2
S.C.
15.4
15.6
15.4
16.2
16.7
16.8
16.9
17.8
18.2
K.W
2.39
2.35
2.32
2.53
2.49
2.46
2.56
2.53
2.50
85
T.C.
25.4
23.9
21.8
25.7
24.6
22.8
26.1
25.2
23.7
S.C.
15.3
15.1
14.4
16.4
16.6
16.2
17.4
18.2
18.1
K.W
2.67
2.62
1.40
2.82
2.76
2.71
2.93
2.88
2.83
95
T.C.
24.4
22.5
19.6
24.9
23.4
20.9
25.4
24.3
22.2
S.C.
15.3
14.6
13.4
16.6
16.6
15.7
17.9
18.5
17.9
K.W
2.71
2.64
2.55
2.86
2.80
2.71
2.91
2.85
2.77
105
T.C.
22.5
20.1
17.6
23.2
21.1
18.6
23.9
22.1
19.6
S.C.
14.7
13.8
12.7
16.4
15.9
14.7
18.1
17.9
16.8
K.W
2.98
2.89
2.80
3.14
3.05
2.95
3.27
3.18
3.08
115
T.C.
20.6
17.7
15.6
21.5
18.8
16.3
22.4
19.8
16.9
S.C.
14.2
13.0
11.9
16.3
15.2
13.8
18.3
17.3
15.6
K.W
3.00
2.88
2.80
3.17
3.05
2.95
3.24
3.12
3.00
125
T.C.
17.8
15.2
13.3
18.7
15.9
14.0
19.5
16.7
14.7
S.C.
13.3
12.4
11.4
15.4
14.3
13.1
17.4
16.1
14.7
K.W
3.13
3.02
2.93
3.30
3.18
3.08
3.37
3.23
3.13
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
N1AHB1293 G2FD030S17
1.00
1.00
1.00
N1AHB1293
G2FD036S17
1.02
1.03
1.03
F2RP036N93
1.02
1.03
1.03