York CZH024 THRU 060 Manuel D’Utilisation

Page de 26
350154-YTG-C-0808
2
Johnson Controls Unitary Products
All dimensions are in inches. They are subject to change without notice. 
Certified dimensions will be provided upon request.
Physical and Electrical Data
MODEL
CZH02411
CZH03611
CZH04811
CZH06011
Unit Supply Voltage
208-230V, 1
φ, 60Hz
Normal Voltage Range 
1
187  to 252
Minimum 
Circuit 
Ampacity
15.6 23.6 29.2 34.8 
Max. Overcurrent Device Amps 
2
25 40 50 60 
Min. Overcurrent Device Amps 
3
20 25 30 35 
Multi-stage 
Compressor
Yes Yes Yes Yes 
Compressor 
Type 
Scroll Scroll Scroll Scroll 
Compressor Amps
Rated 
Load
10.3 16.7 21.2 25.6 
Locked 
Rotor
52 82 96 118 
Crankcase 
Heater
No No No No 
Fan Motor Amps
Rated Load
2.8 
2.8 
2.8 
2.8 
Fan 
Diameter 
Inches
24 24 24 24 
Fan Motor
Rated 
HP
1/3 1/3 1/3 1/3 
Nominal 
RPM
685 685 685 685 
Nominal 
CFM
2900 3200 3100 3150 
Coil
Face Area Sq. Ft.
23.58 
23.58 
23.58 
23.58 
Rows 
Deep
2 2 2 2 
Fins 
Inch
16 16 14 14 
Liquid Line Set OD (Field Installed)
3/8 
3/8 
3/8 
3/8 
Vapor Line Set OD (Field Installed)
3/4 
3/4 
7/8 
7/8 
Unit Charge (Lbs. - Oz.) 
4
15 - 1 
13 - 7 
12 - 9 
13 - 5 
Charge Per Foot, Oz.
0.62 
0.62 
0.67 
0.67 
Operating 
Weight 
Lbs.
305 305 310 330 
1
Rated in accordance with ARI Standard 110, utilization range “A”.
2
Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3
Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4
The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, 
add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
VAPOR
LIQUID
2-3/8
3-1/8
6-1/2
C
A
B
Unit
Model
Dimensions
(Inches)
Refrigerant 
Connection  
Service Valve Size
A
B
C
Liquid
Vapor
24
39-1/2 42  34 
3/8”
3/4”
36 39-1/2 42  34 
48
39-1/2 42  34 
7/8”
60 39-1/2 42  34