Raypak 2342BE Manuel D’Utilisation

Page de 5
 
Project Name / Date 
 
Division 23 52 33.13 - 1 
 
 
 
DIVISION 23 52 33.13 
 
FINNED WATER-TUBE BOILERS 
PART 1 - GENERAL 
1.1 SUMMARY 
A.  Section includes gas-fired, copper finned-tube hydronic heating boilers 
B. Related 
Sections 
Specifier Note:  Use as needed 
1.  Building Services Piping – Division 23 21 00 
2.  Breeching, Chimneys, and Stacks (Venting) – Division 23 51 00 
3.  HVAC Instrumentation and Controls – Division 23 09 00 
4.  Electrical – Division 23 09 33 
1.2 REFERENCES 
A.  ANSI Z21.13/CSA 4.9 
B.  ASME, BPV Section IV 
C.  2006 UMC, Section 1107.6 
D.  ANSI/ASHRAE 15-1994, Section 8.13.6 
E.  National Fuel Gas Code, ANSI Z223.1/NFPA 54 
F. I=B=R 
G.  National Electrical Code. ANSI/NFPA 70 
H.  ASME CSD-1, 2009 (when required) 
1.3 SUBMITTALS 
A.  Product data sheet (including dimensions, rated capacities, shipping weights, accessories) 
B. Wiring 
diagram 
C. Warranty information 
D.  Installation and operating instructions 
1.4 QUALITY 
ASSURANCE 
A. Regulatory 
Requirements 
1.  ANSI Z21.13/CSA 4.9 
2.  Local and national air quality regulations for low NOx (< 20 PPM NOx emissions) boilers  
B. Certifications 
1. CSA 
2.  ASME H Stamp and National Board Listed 
3. ISO 
9001 
1.5 WARRANTY 
A.  Limited one-year warranty from date of installation  
B.  Limited twenty-year thermal shock warranty 
C.  Limited ten-year closed-system heat exchanger warranty 
PART 2 - PRODUCTS 
2.1 MANUFACTURER 
A. Raypak, 
Inc. 
1.  Contact: 2151 Eastman Ave., Oxnard, CA 93030; Telephone: (805) 278-5300;  
 
Catalog No.:  2000.952D
Effective: 9-1-09
Replaces: 5-1-08
HI DELTA
®
, TYPE H - MODELS 992BE-2342BE 
SUGGESTED SPECIFICATIONS