S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
65-0303—05
38
DETAILS
Details of the hydronic or steam system is accomplished 
through the detail status pages. The detail status page is 
shown below.
Screens will appear only if they are configured for your system.
Information shown is current status. For example: firing rate is 
the current fan speed or motor position; timing shown is current 
time Sola is at.
Fig. 70. Hydronic CH detail status page.
Status information on the detail status page is organized into 
groups and displayed on the page one group at a time. The 
user moves from one group to another using the left and right 
arrow buttons.
Status data on the detail status page is displayed in a menu for 
the group that is currently displayed. If more status items exist 
in the group than will fit on the screen, a vertical scroll bar 
allows the user to see all status data. If the user selects a line 
of status data in the menu, it will expand in bigger, more easily 
readable text, as show in Fig. 71. Additional information about 
Status data and groups that are displayed are provided in the 
R7910A or R7911 Status section of this document.
Fig. 71. Hydronic “expanded” detail status.
R7910A or R7911 Status
Data in Tables 45–Table 56 are displayed on the R7910A 
Hydronic or R7911 Steam status pages. A complete list of 
Status tables can be found in Table 60 on page 53.
The CH status data shown in Table 45 displays first when the 
CH Hydronic heating loop is selected on the Home page.
Fig. 72. CH Hydronic Status menu (top).
Table 45. CH Hydronic Status.
Data Comment 
CH enable 
Enabled, Disabled
CH burner demand
On or Off
CH pump
On or Off
CH pump demand
On or Off
CH pump overrun 
time
Running overtime for CH pump 
(seconds)
CH requested rate
RPM or %
CH OFF setpoint
Setpoint plus hysteresis
CH setpoint
Temp setting between -40 °F to 266 °F 
(-40 °C to 130 °C)
CH ON setpoint
Setpoint minus hysteresis 
CH setpoint source
Normal, TOD, Outdoor reset, Remote 
control
CH status
Disabled, Normal, Suspended
Demand source
Sensor only, Sensor and Stat terminal, 
Sensor and Remote Stat, LCI and 
sensor
Outlet high limit
Yes or No
Outlet high limit 
setpoint
Temp setting between -40 °F to 266 °F 
(-40 °C to 130 °C)
Outlet sensor state
None, Normal, Open, Shorted, 
Outside high range, Outside low 
range, Not reliable (None = no outlet 
sensor)
Outlet temperature
Outlet temperature (same as bar 
graph)