S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
65-0303—05
46
Fig. 94. Diagnostics analog I/O page (left).
Fig. 95. Diagnostics analog I/O page (center).
Fig. 96. Diagnostics analog I/O page (right).
INSTALLER CHECKOUT
Diagnostics Tests
Pressing the Diagnostics Test button launches the diagnostic 
tests. The first test displayed on the right side of the screen is 
the last selected test shown, as seen in Fig. 97.
This screen enables the user to perform the following tests:
Modulation Test: enables the user to verify that the burner is 
firing at the correct rate. (See Fig. 97.)
Pilot Test: enables the user to verify that the pilot valve is 
functioning properly. The user can also perform burner 
adjustments for the pilot flame. (See Fig. 98.)
Pump Test: enables the user to verify that the correct pump is 
on or off. The Start Test button will test all pumps; pressing an 
individual pump tests that pump only. (See Fig. 99.)
Burner Switch: this button turns the burner on or off.
Start Test: runs the test for 5 minutes.
Fig. 97. Modulation test.
Fig. 98. Pilot test.