Emerson 2400S Manuel D’Utilisation

Page de 50
Installation Manual
39
Dimensions and Specifications
Re
tu
rn
 P
o
li
cy
 
In
de
x
Spec
ifications
A.9
Environmental limits
A.10
Environmental effects
A.11
Hazardous area classifications
Ambient temperature limits
Operating and storage: –40 to +140 °F (–40 to +60 °C)
Below –4 °F (–20 °C), LCD responsiveness decreases and LCD may become 
difficult to read. Above 131 °F (55 °C), some darkening of the LCD panel might 
occur.
ATEX requires limiting ambient temperature to below 131 °F (55 °C).
Humidity limits
5 to 95% relative humidity, non-condensing at 140 °F (60 °C)
Vibration limits
Meets IEC68.2.6, endurance sweep, 5 to 2000 Hz, 50 sweep cycles at 1.0 g
All models
EMI effects
Meets EMC directive 89/336/EEC per EN 61326 Industrial
Conforms to NAMUR NE21 Version: 10.02.2004
Model 2400S Analog only
Ambient temperature effect
On mA output: ±0.005% of span per °C
All models
CSA
(1)
 C-US
(1) CSA is a Canadian approvals agency that provides approvals accepted both in the U.S.A. and in Canada. 
Class I Division 2 Groups A, B, C, D
Class II Division 2 Groups F and G
ATEX
(2)
(2) ATEX is a European directive.
Zone 1 Analog
II 2GD EEx mb e ib IIC T4
Zone 2 Analog or 
PROFIBUS-DP
II 3G EEx n A C II T5
II 3D IP66/IP67 T70°C
Zone 2 DeviceNet
II 3G Ex nA II T5
II 3D IP66/IP67 T70°C