INSTALLATION – SOLAR COLLECTORS 
37 
• 
The installation must comply with the requirements of AS/NZS 3500.4 and 
all local codes and regulatory authority requirements. 
• 
Refer to the installation instructions supplied with the collector kit for details 
on the installation of the solar collectors. 
 
LATITUDE OF SOME AUSTRALIAN CITIES 
 
Adelaide 
35
°S  Cairns 
17
°S  Hobart 
42
°S  Port Hedland 
20
°S 
Alice Springs 
24
°S  Canberra 
35
°S  Mildura 
34
°S  Rockhampton  24°S 
Brisbane 
27
°S  Darwin 
12
°S  Melbourne 
38
°S  Sydney 
34
°S 
Broken Hill 
31
°S  Geraldton 
28
°S  Perth 
32
°S  Townsville 
19
°S 
 
PIPE LENGTHS 
The maximum recommended combined length of the solar cold and solar hot 
pipes with bends is: 
 
Maximum recommended total combined pipe length and number of 90
° bends 
1 or 2 Collectors 
3 Collectors 
4 Collectors 
Pipe 
Size 
Pipe Length  90
° Bends
Pipe Length  90
° Bends Pipe Length  90° Bends 
DN15 
40 metres 
20 
30 metres 
20 
15 metres 
20 
DN20 
NR 
NR 
40 metres 
20 
40 metres 
20 
For each additional 90
° bend, reduce the maximum total pipe length by 0.5 metres. 
For each additional metre of pipe length, reduce the number of 90
° bends by two. 
Note: One 90
° elbow is equal to two 90° bends. 
NR – not recommended. 
 
The solar hot and solar cold pipes between the solar storage tank and the solar 
collectors should be a minimum DN15. 
 
Maximum height to collectors 
The maximum height of a solar Loline installation, from the solar controller 
(circulator) to the top of the solar collectors, is determined by the maximum 
recommended total pipe length for the system and the water supply pressure. 
 
The maximum recommended total pipe length of the solar circuit should not be 
exceeded and a minimum water supply pressure of 200 kPa should be 
available at the inlet to the system, otherwise the system performance may be 
reduced or the solar circuit may not be purged of air during the commissioning 
of the system.