InSTalleR SeTuP
To begin, press and hold the s and FAN buttons until 
the display changes.
Press s
 
or t to change settings.
Press NEXT to advance to the next function.
Press DONE to exit and save settings.
Proceed to Installer Setup Functions on page 4.
1.
2.
3.
4.
5.
To begin, press and hold the s and FAN buttons until 
the display changes.
Press s
 
or t to change settings.
Press NEXT to advance to the next function.
Press DONE to exit and save settings.
Proceed to Installer Setup Functions on page 4.
1.
2.
3.
4.
5.
InSTalleR SeTuP FuncTIOnS
Available option and default settings vary by thermostat.
Table 1. Installer Setup
Setup functions
Setting & Options  
(factory default in bold)
1
System type
1 heat / 1 cool Conv.
1 heat / 1 cool heat 
pump (no Aux. heat)
Heat only (2-wire, 3-wire 
zone valves [Series 20], 
and normally open zone 
valves)
Heat only with fan
Cool only
2 heat / 1 cool heat 
pump (with Aux. heat)
2 heat / 2 cool Conv.
2 heat / 1 cool Conv.
1 heat / 2 cool Conv.
2 heat / 2 cool heat pump 
(no Aux. heat)
10 
3 heat / 2 cool heat 
pump (with Aux. heat)
2
Changeover valve 
(O/B terminal)
Controls valve in cooling
Controls valve in heating
3
Fan control 
(heating)
Gas/Oil heat (equipment 
controls heating fan)
Electric furnace (thermo-
stat controls heating fan)
5
First stage heat 
cycle rate
Gas or oil furnaces of 
less than 90%  
efficiency
Steam or gravity
Hot water systems or fur-
naces of 90%+ efficiency
Electric furnaces 
[Other options: 1–12]
6
Second stage 
heat/Aux heat 
cycle rate
Gas or oil furnaces of 
less than 90% efficiency
Steam or gravity
Hot water systems or fur-
naces of 90%+ efficiency
Electric furnaces 
[Other options: 1–12]
7
Auxiliary heat 
cycle rate
Gas or oil furnaces of 
less than 90% efficiency
Steam or gravity
Hot water systems or fur-
naces of 90%+ efficiency
Electric furnaces 
[Other options: 1–12]
Table 1. Installer Setup
Setup functions
Setting & Options  
(factory default in bold)
8
Emergency heat 
cycle rate
Electric emergency heat
Steam or gravity
Hot water systems or fur-
naces of 90%+ efficiency
Gas or oil furnaces of 
less than 90% efficiency 
[Other options: 1–12]
9
First stage 
compressor cycle 
rate
Recommended 
[Other options: 1–6]
10
Second stage 
compressor cycle 
rate 
Recommended 
[Other options: 1–6]
12
Manual/Auto 
changeover
Manual changeover 
(Heat/Cool/Off)
Auto changeover (Heat/
Cool/Auto/Off)
Auto changeover only 
(Auto)
13
Adaptive Intel-
ligent Recovery
TM
On
Off
14
Temperature 
display
Fahrenheit
Celsius
15
Compressor 
protection
5-minute compressor 
off time 
[Other options: 0–4 
minutes]
16
Schedule format
5/2 (weekdays  
and weekends  
programmable)
5/1/1 (weekdays, 
Saturday, and Sunday 
programmable)
26
Auxiliary heat 
control
Comfort
Economy
27
Heat temperature 
range stops
90 
Max. heat temperature 
setting is 90°F (32°C) 
[Other options: 40–89°F 
(4.5°C to 32°C)]
28
Cool temperature 
range stop
50 
Min. cool temperature 
setting is 50°F (10°C) 
[Other options: 51–99°F 
(10.5°C to 37°C)]
Functions 13 and 16 only available on the 6000 series; 
function 26 only available on the 5000 series
1
0
Done
Next
1
0
Done
Next
Function 
 
Setting
FocusPRO
®  
6000 Series
Function 
 
Setting
FocusPRO
®
 5000 Series