Water Pressure: A minimum of 25 pounds of water pressure 
(psi) is required for regeneration.  Maximum 125 psi.
Water Quality: On rural water supplies there is often a problem 
with sand or sediment in the water. (This problem occasionally 
occurs in public water supplies.) If the water is not filtered before 
being softened, the sand and sediment will plug up the water 
softener restricting the flow through the resin bed. This problem 
often requires rebedding of the mineral tank. Note: Well and/
or pump problems affecting the operation of the softener are 
repairs that are not covered under warranty. To prevent these 
unnecessary, and expensive repairs not covered under warranty, 
we recommend the installation of an in-line filter system ahead 
of the softener.
Electrical: A  continuous  110  volt,  60  cycle  current  supply  is 
required. Make certain the current supply is uninterrupted and 
cannot be turned off with another switch.  All electrical connec-
tions must be connected per local codes.  
Surge protection is 
recommended with all electric controls.
Existing  Plumbing:  Condition  of  existing  plumbing  must  be 
free from lime and iron build-up. Piping that is built-up heavily 
with lime and/or iron must be replaced. If piping is blocked with 
iron, additional equipment must be installed ahead of the water 
conditioner to correct the problem.
Drain Line: The conditioner should be located close to a drain. 
Avoid overhead drain lines if possible to prevent back pressure 
on the brine injector. Overhead drains are not to exceed 8 feet 
above the floor and no more than 20 feet in length.  The pipe 
size for the drain line should be a minimum of 3/4”.  Backwash 
flow rates in excess of 7 gpm or length in excess of 20’ require 
1” drain line.
Bypass Valves: Always provide for the installation of a bypass 
valve. 
Softening: It is recommended that the conditioner be installed 
to soften both the hot and cold water supply. A separate hard 
water faucet may be plumbed for drinking purposes if you desire. 
Outside faucets should be left on hard water.
Caution: Water temperature is not to exceed 110°F; the condi-
tioner cannot be subject to freezing conditions, or to a vacuum 
due to loss of pressure (such as a water main break).
pre-insTallaTiOn CheCk lisT
Figure 5
Figure 4
(All electrical & plumbing should be done in accordance to all local codes)
Figure 2
Figure 3
bYpass valve OperaTiOn