DEFINITY Enterprise Communications Server Release 6
Installation and Test for Multi-Carrier Cabinets  
555-230-112  
Issue 5
May 1998
Install and Connect Cabinets 
Page 1-15
Connect AC Power and Ground 
1
Figure 1-5.
Shorting Cable Installation
1. Set the circuit breakers on the power distribution unit OFF. See 
Figure 1-5
.
2. At the rear of the cabinet, insert the shorting cable (H600-442-G1) into 
J11. The cable is keyed so it can fit only 1 way.
Connect AC Power
1. Set the main circuit breakers on the power distribution unit OFF.
2. Connect cabinet AC line cords to the AC power receptacles.
3. Do not power up the system at this time.
Figure Notes
1. Shorting Cable (H600-442-G1) (If 
Battery Charger is Not Installed)
2. J11