WIRE SIZES 
 
The following chart contains information on wire sizes, the DC resistance of the wires and the corresponding diameters and areas of 
these wires.  This information can be used to calculate the voltage drop of the wires or to find an equivalent wire size. 
 
CROSS-SECTIONAL AREA
 
APPROXIMATE 
DIAMETER 
SIZE
 
(AWG) 
DC 
Resistance 
in Ohms 
(1000 feet)
 
SQUARE
INCHES
 
SQUARE 
MILLIMETERS
 
INCHES
 
MILLIMETERS
 
14 
3.14 
.0032 
2.08 
.078 
1.98 
12 
1.98 
.0051 
3.31 
.101 
2.57 
10 
1.24 
.0082 
5.26 
.126 
3.20 
8 
0.78 
.0130 
8.37 
.162 
4.11 
6 
0.50 
.0206 
13.30 
.215 
5.46 
4 
0.31 
.0328 
21.15 
.269 
6.83 
2 
0.19 
.0521 
33.62 
.337 
8.56 
1 
0.15 
.0657 
42.41 
.376 
9.55 
1/0 
0.12 
.0829 
53.50 
.423 
10.74 
2/0 
0.10 
.1045 
67.43 
.508 
12.90 
3/0 
0.08 
.1318 
85.01 
.576 
14.63 
4/0 
0.06 
.1662 
107.20 
.645 
16.38