Telect MIX 56 Manuel D’Utilisation

Page de 124
2  Installation
MIX 56 User Manual
2-4
Telect, Inc. 122188-10 A0
3/8 in. open-end or socket wrench to attach chassis ground wire to 
ground stud
Wire-wrap tool to attach front cross-connects when used as DSX or to 
connect DS1 signals to M13 when used as multiplexer
Also, you must supply 14 AWG (minimum) insulated, stranded wire for 
grounding, and a groundable shielded cable for the ethernet port.
Power
CAUTION
!
CAUTION!  Do not supply power until all connections are made 
in accordance with requirements specified in local electrical 
codes.
ALERT
!
ALERT!  Protect this equipment with a listed/approved branch 
circuit breaker sufficiently rated to interrupt power at either 
–48 Vdc at 1 amp, or 24Vdc at 2 amp. The panel must be acces-
sible when operating the unit.
The chassis must receive 20Vdc to 60Vdc. Since MIX 56 includes active 
components, Telect recommends using a dual feed panel to provide input 
power redundancy.
Technical Support (USA)
By e-mail: getinfo@telect.com
By phone: 888-821-4856 or 509-921-6161
I
NSPECTION
Compare the contents of the MIX 56 shipping container with the packing 
list. Call Telect if you are missing anything.
NOTE
Telect is not liable for shipping damage.
If the shipping container is damaged, keep it for the carrier’s inspection.
Notify the carrier and call Telect’s Customer Service Department: