6. Appendices
These bits go to 1 when the current in a
corresponding output circuit is greater than
the minor alarm threshold (60% in the
example opposite) and less than the major
alarm threshold (80% in the example
opposite). This state is stored in memory
until the alarm is reset by setting the bit to 0.
#
Bit
R/W
NV
Description
1
R
Current in circuit  01
2
R
Current in circuit  02
...
...
......
...
...
......
41
R
Current in circuit  41
42
R
Current in circuit  42
43
R
NV
Global alarm register
0
for the register with address 44
1
for the register with address 45
2
for the register with address 46
3
for the register with address 47
4
for the register with address 48
5
for the register with address 49
6 to 15
Unused bits
44
R/W
NV
Minor alarms on circuits 1 to 16
0
60% < Current in circuit 01 < 80%
1
60% < Current in circuit 02 < 80%
2
60% < Current in circuit 03 < 80%
3
60% < Current in circuit 04 < 80%
4
60% < Current in circuit 05 < 80%
5
60% < Current in circuit 06 < 80%
6
60% < Current in circuit 07 < 80%
7
60% < Current in circuit 08 < 80%
8
60% < Current in circuit 09 < 80%
9
60% < Current in circuit 10 < 80%
10
60% < Current in circuit 11 < 80%
11
60% < Current in circuit 12 < 80%
12
60% < Current in circuit 13 < 80%
13
60% < Current in circuit 14 < 80%
14
60% < Current in circuit 15 < 80%
15
60% < Current in circuit 16 < 80%
45
R/W
NV
Minor alarms on circuits 17 to 32
0
60% < Current in circuit 17 < 80%
1
60% < Current in circuit 18 < 80%
2
60% < Current in circuit 19 < 80%
3
60% < Current in circuit 20 < 80%
4
60% < Current in circuit 21 < 80%
5
60% < Current in circuit 22 < 80%
6
60% < Current in circuit 23 < 80%
7
60% < Current in circuit 24 < 80%
8
60% < Current in circuit 25 < 80%
9
60% < Current in circuit 26 < 80%
10
60% < Current in circuit 27 < 80%
11
60% < Current in circuit 28 < 80%
12
60% < Current in circuit 29 < 80%
13
60% < Current in circuit 30 < 80%
14
60% < Current in circuit 31 < 80%
15
60% < Current in circuit 32 < 80%
46
R/W
NV
Minor alarms on circuits 33 to 42
0
60% < Current in circuit 33 < 80%
1
60% < Current in circuit 34 < 80%
2
60% < Current in circuit 35 < 80%
3
60% < Current in circuit 36 < 80%
4
60% < Current in circuit 37 < 80%
5
60% < Current in circuit 38 < 80%
6
60% < Current in circuit 39 < 80%
7
60% < Current in circuit 40 < 80%
8
60% < Current in circuit 41 < 80%
9
60% < Current in circuit 42 < 80%
10 to 15
Unused bits (all set to 0)
Each element represents the value in mA of
the current in the given output circuit.
Cards BCM1, BCM2 and BCM3 (status and measurements for 42 or 21 output circuits
of one phase)
This register provides a rapid overview of
the status of the alarms on the card.
The global alarm bit is 1 if any one of the 16
bits of the indicated register is 1.
All the variables are whole numbers.