MGE UPS Systems 30A Manuel D’Utilisation
34020113EN/AA
- Page 25
4. Maintenance
4.1 Identification of anomalies
4.2 Transfer to the manual bypass
Transfer to the manual bypass for source
S1:
S1:
1 - Manually transfer the load to source S1.
2 - Set switch Q2 4 to the OFF position
(position 0).
(position 0).
3 - Set switch Q1BP 6 to the ON position
(position 1).
(position 1).
The load is supplied by source S1 via the
bypass.
bypass.
4 - Set switches Q1 1 and Q3 7 to the
OFF position (position 0).
OFF position (position 0).
The operation for source S2 is
identical, using switches Q2 and
Q2BP.
identical, using switches Q2 and
Q2BP.
Interlocking of the bypass lines is
ensured by use of a single key that
must be inserted on the bypass
switch to be operated.
ensured by use of a single key that
must be inserted on the bypass
switch to be operated.
General-alarm
LED 21
-
-
-
-
-
S1 31 or S2 32
LED
-
-
-
-
Static-switch
LED 33 or 34
-
-
-
-
-
The meaning of all these anomalies are detailed on the display:
Select the alarm: the corresponding informations are displayed.
Select the alarm: the corresponding informations are displayed.
Buzzer
Beeps
Beeps
Beeps
Beeps
-
-
Meaning
Internal STS fault.
Source outside
tolerances, load still
supplied.
tolerances, load still
supplied.
Source outside
tolerances, no voltage.
The load cannot be
supplied by this source.
tolerances, no voltage.
The load cannot be
supplied by this source.
Static-switch fault.
Overload.
Load not supplied.
System output
LED 38
-
-
-
-
Q1
Q5 Q6
Q2
Q1BP
Q2BP
Q3
0
1
0
1
0
0
0
1
1
1
Q1
Q5 Q6
Q2
Q1BP
Q2BP
Q3
0
1
0
1
0
0
0
1
1
1
Q1
Q5 Q6
Q2
Q1BP
Q2BP
Q3
0
1
0
1
0
0
0
1
1
1
1
4
6
7