MGE UPS Systems 30A Manuel D’Utilisation

Page de 30
 34020113EN/AA 
- Page 25
4. Maintenance
4.1 Identification of anomalies
4.2 Transfer to the manual bypass
Transfer to the manual bypass for source
S1:
1 - Manually transfer the load to source S1.
2 - Set switch Q2   4   to the OFF position
(position 0).
3 - Set switch Q1BP   6   to the ON position
(position 1).
The load is supplied by source S1 via the
bypass.
4 - Set switches Q1   1   and Q3   7   to the
OFF position (position 0).
The operation for source S2 is
identical, using switches Q2 and
Q2BP.
Interlocking of the bypass lines is
ensured by use of a single key that
must be inserted on the bypass
switch to be operated.
General-alarm
LED   21
-
-
-
-
-
S1  31  or S2  32
LED
-
-
-
-
Static-switch
LED  33  or  34
-
-
-
-
-
The meaning of all these anomalies are detailed on the display:
Select the alarm: the corresponding informations are displayed.
Buzzer
Beeps
Beeps
Beeps
Beeps
-
-
Meaning
Internal STS fault.
Source outside
tolerances, load still
supplied.
Source outside
tolerances, no voltage.
The load cannot be
supplied by this source.
Static-switch fault.
Overload.
Load not supplied.