American Aldes DHV-150H Manuel D’Utilisation

Page de 19
 
12
in the compressor motor, the resulting high 
temperature arc causes a portion of the refrigerant oil 
mixture to break down into carbonaceous sludge, a 
very corrosive acid, and water. These contaminants 
must be carefully removed otherwise even small 
residues will attack replacement compressor motors 
and cause failures. 
 
The following procedure is effective only if the system 
is monitored after replacing the compressor to insure 
that the clean up was complete. 
 
1.  This procedure assumes that the previously 
listed compressor motor circuit tests revealed a 
shorted or open winding. 
 
2.  Remove and properly dispose of the system 
charge. DO NOT vent the refrigerant or allow it 
to contact your eyes or skin. 
 
3.  Remove the burned out compressor. Use rubber 
gloves if there is any possibility of contacting the 
oil or sludge. 
 
4.  To facilitate subsequent steps, determine the 
type of burn out that occurred. If the discharge 
line shows no evidence of sludge and the 
suction line is also clean or perhaps has some 
light carbon deposits, the burn out occurred 
while the compressor was not rotating (standing 
burn out). Contaminants are therefore largely 
confined to the compressor housing. A single 
installation of liquid and suction line filter/driers 
will probably clean up the system. 
 
If sludge is evident in the discharge line, it will 
likely be found in the suction line. This indicates 
the compressor burned out while running 
(running burn out).  Sludge and acid have been 
pumped throughout the system. Several 
changes of the liquid and suction filter/driers will 
probably be necessary to cleanse the system. 
 
5.  Correct the system fault that caused the burn 
out. Consult the factory for advice. 
 
6.  Install the replacement compressor with a new 
capacitor and an oversized liquid line filter. 
 
In a running burn out, install an oversized 
suction line filter/drier between the accumulator 
and compressor. Thoroughly flush the 
accumulator with refrigerant to remove all 
trapped sludge and to prevent the oil hole from 
becoming plugged. A standing burn out does not 
require a suction line filter/drier. 
 
7.  Evacuate the system with a good vacuum pump 
and accurate vacuum gauge. Leave the pump 
on the system for at least an hour. 
 
8.  Operate the system for a short period of time, 
monitoring the suction pressure to determine that 
the suction filter is not becoming plugged. 
Replace the suction filter/drier if pressure drop 
occurs. If a severe running burn out has 
occurred, several filter/driers may have to be 
replaced to remove all of the acid and moisture. 
 
NOTE:  NEVER use the compressor to evacuate 
the system or any part of it. 
 
5.6C Replacing a Compressor, Nonburn 
Out 
 
Remove the refrigerant from the system. Replace the 
compressor and liquid line filter/drier. Charge the 
system to 50 PSIG and check for leaks. Remove the 
charge and weigh in the refrigerant quantity listed on 
the nameplate. Operate the system to verify 
performance. 
 
5.7 Remote Controls
 
 
Devices mounted on a panel that is remote from the 
unit control the DHV-150H. You may or may not have 
the devices listed below depending on the model of 
the remote control panel that you purchased. If the 
DHV-150H fails to operate as desired, always check 
the settings of the controls to insure that they are 
correct. Check that the controls are receiving 24Vac 
from the DHV-150H. Check the connections between 
the DHV-150H, the control panel, and the field control 
wiring. 
 
5.7A Humidity Control 
 
The humidity control is an adjustable switch that closes 
when the relative humidity of the air in which it is 
located rises to the dial set point. It opens when the 
RH drops 4 to 6% below the set point. If the DHV-
150H does not run, try turning the humidity control 
clockwise until it reaches the stop and the knob pointer 
points at “Max Dry” (see back of control panel cover.) 
 
The DHV-150H is equipped with an automatic defrost 
mechanism. If the DHV-150H operates in conditions 
that develop frost on the evaporator, it will sense the 
frost build-up and automatically defrost the evaporator. 
The DHV-150H may not appear to be operating 
correctly during the defrost sequence, but once the 
defrost sequence is completed, the DHV-150H will 
resume dehumidifying.