11.  POINTS TO DIAGNOSE
11-1.  Indoor Unit Alarm Signal
11-2.  Manifold Pressure
To set manifold pressure there are 2 settings – low pressure and high pressure.
Use SW1 to move to the 2 modes used to adjust the two pressures.
Press SW1 1 time for low pressure.
Press SW1 2 times for high pressure.
Press SW1 3 times for normal operation.
Use VR1 to set the low, lighting pressure and VR2 to set the high pressure.
Step 1: Set low pressure
1. Press SW1 and hold until LEDs 4 and 5 flash.
2. Adjust the low pressure with VR1 to 0.63 inches of water column.
Step 2: Set high pressure
1. Press SW1 again and LEDs 1 and 2 will flash.
2. Adjust pressure with VR2 to 3.43 inches of water column.
Step 3: Set lighting pressure
Lighting pressure will be set automatically from Step 1 and Step 2.
Check these settings 2 or 3 times to insure all are correct then reset until no LEDs flash.
NOTE
Alarm Signal
Error Meaning
Operation
Information
Misconnection of inter-unit wiring
Heating • Cooling • Dry
Connect correctly
Room temp. thermistor is defective
Heating • Cooling • Dry
Normal: 9 – 11 k
Ω
at 50°F 
4 – 6 k
Ω
at 77°F
Power Lamp Heat exch. thermistor is defective
Heating • Cooling • Dry
Normal: 100 – 120 k
Ω
at 50°F 
Flashing
50 – 60 k
Ω
at 77°F
Fan motor is defective
Heating • Cooling • Dry
Alarm signal appears in 1 min.
Amp. current is high
Heating • Cooling • Dry
More than 17 amp.
Amp. current is low
Heating • Cooling • Dry
Less than 0.8 amp.
Heat exch. thermistor detects high temp
Heating
More than 154°F (68°C)
Outdoor Unit
Fuel
Inlet Pressure W.C. (kPa)
Manifold Pressure  W.C. (kPa)
Low
High
Lighting (10 sec.)
LD4, 5 Flashing
LD2, 3 Flashing
(verification)
CG1411
Natural gas
7.0 (1.74)
0.63 (0.157)
3.43 (0.853)
2.32 (0.579)