Specifications and Technical Data 
 
Model 
KFHHP-18-ID / KFHHP-18-OD 
Function 
Heating and Cooling 
Cooling capacity(BTU/hr) & (Watts) 
18000 / 5300 (1400-6000) 
Heating capacity(BTU/hr) & (Watts) 
20000 / 6000 (1100-7000) 
Rated voltage 
208-230V~ 
Rated Frequency 
60Hz 
Cooling/Heating rated current(A) 
10.6/10.6 
Cooling/Heating rated power(W) 
2440/2440 
Cooling/Heating power input(W) 
1350/1800 
SEER 13.25 
EER/COP(W/W) 3.93/3.22 
HSPF 8.5 
Recycling Air Volume(m
3
/h) 
800 
Factory Charge 410A (lbs.)* 
R410A    3.9 lbs
 
Noise (Indoor/Outdoor) dBA 
50/57 
Maximum Vertical 
16.4 ft 
Height Differential 
Maximum Length 
32.8 ft 
Net Weight (Indoor/Outdoor) (lb) 
28.7/130.1 
Dimensions (Indoor/Outdoor) 
(WxDxH)(inch) 
Indoor unit :40.16” × 8.98” ×12.20” 
Outdoor unit:37.40” × 13.39” × 26.93” 
 
Connection Pipe: 
Length (ft) 
26.25 
Gas additional charge(oz/ft) 
0.21 
Liquid Pipe (mm) 
Φ
9.52(5/8”) 
Outer Diameter 
Gas Pipe (mm) 
Φ
16(3/8”) 
Height (ft) 
26.25 
Max Distance 
Length (ft) 
49.21 
 
™  All above are tested and certified to ETL specification. Among them, the cooling capacity, heating 
capacity and noise level are tested before shipment. 
™  In case of any change in performance parameters, the data provided on nameplate shall prevail. 
™ 
Test the maximum input power under maximum cooling condition (89.6°F /73.4°F, 109.4°F /78.8°F) 
and maximum heating condition (44.6°F /-, 75.2°F /69.8°F). 
 
™  Working temperature range 
 
 
Indoor side DB/WB(°F) 
Outdoor side DB/WB(°F) 
Maximum cooling 
89.6 / 73.4 
109.4 / 78.8(T1) 
Minimum cooling 
69.8 / 59 
64.4 / - 
Maximum heating 
80.6 / - 
75.2 / 64.4 
Minimum heating 
68 / - 
19.4 / 17.6