ADC truenet four-pair riser cable Manuel D’Utilisation

Page de 4
5/08
104976AE
 
CopperTen
®
 Four-Pair 
Riser 
Cable
TrueNet
®
CopperTen
®
 Four-Pair Riser Cable
2
w w w . a d c . c o m  
•  
+ 1 - 9 5 2 - 9 3 8 - 8 0 8 0  
•  
1 - 8 0 0 - 3 6 6 - 3 8 9 1
Specifications
CONSTRUCTION CHARACTERISTICS 
  Conductor:
 
23 AWG solid bare copper
  Insulation: 
100% Polyolefin
  Separator: 
Flame retardant polyolefin
  Jacket: 
Non-lead, flame retardant PVC
  Nominal Outer Diameter:
7.5 mm (.295") – 6.6 mm x 8.3 mm (.260" x .325")
MECHANICAL CHARACTERISTICS
  Bend Radius
   During Installation:
8 x outer diameter
   Installed:
4 x outer diameter
   Pull Tension: 
110 N (25#)
ELECTRICAL CHARACTERISTICS
  Conductor DC Resistance @ 20° C (68° F) (Max):
 
9.38 
Ω/100 m (28.6 Ω/1000 ft)
  DC Resistance Unbalance (Max): 
2%
  Mutual Capacitance @ 20° C (68° F) (Max): 
5.6 nF/100 m (17 pF/ft)
  Operating Voltage (Max): 
300 VDC
  Worst Case Cable Skew: 
40 ns/100 m (40 ns/ 328 ft)
 
  Nominal Velocity of Propagation: 
65%
ENVIRONMENTAL CHARACTERISTICS
  Transport and Storage: 
-20° to 75° C (-4° to 167° F)
 
  Installation: 
4° to 50° C (39° to 122° F)
 
  Operation: 
-20° to 75° C (-4° to 167° F)