Set Up and Calibration Procedures 
Maintenance Set Up Group 
Revision 7 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
59 
7/08  
 
 
Maintenance Set Up Group 
The Maintenance set up group consists of information about actuator operation accumulated through time.  
This information (or maintenance statistics) can be used to evaluate actuator operation and determine 
predicted or scheduled maintenance periods.  Table 22 lists the parameters and selections available for the 
SET MAINTENANCE group.  
Please note that maintenance statistics are written to the EEPROM every 8 hours.  Therefore the statistics 
are saved in the event of a power interruption.   
 
Table 22 Maintenance Set Up Group Parameters 
Actuator Lower 
Display 
Prompt 
Selections or 
Range of Setting  
Parameter Definition/PDA HercuLink
®
 Prompt 
PDA users: The prompts are organized differently on your PDA’s 
HercuLink
®
 
software. Grayed prompts are under Configuration, Maintenance. Non-grayed 
prompts are under Maintenance.
 
TEMP 
nnnn F * 
ACTUATOR TEMPERATURE
— Read Only.  Displays the 
current internal temperature of the actuator. 
TEMPHI 
nnnn F * 
 
HIGH TEMPERATURE LIMIT
— Displays the high 
temperature limit of the internal actuator temperature since it 
was last reset.  
TEMPLO 
nnnn F * 
LOW TEMPERATURE LIMIT
— Displays the low 
temperature limit of the internal actuator temperature since it 
was last reset.   
hh:mm:ss  
ACST   
ACCUMULATED STALL TIME
 Displays the accumulated 
stall time of the actuator motor since it was last reset.   
STARTS 
nnnn 
ACCUMULATED MOTOR STARTS
— Displays the 
accumulated motor starts since it was last reset.  Multiply 
displayed value times 10
5
 to get actual value.  Range is 0 to 
999,900,000. 
RLnCNT 
n
 = 1, 2, 3 or 4 
nnnn 
RELAY CYCLE COUNTS
 Displays the accumulated cycle 
counts of a relay since it was last reset.  One relay cycle is 
when a relay is energized and deenergized. Multiply 
displayed value times 10
to get actual value.  Range is 0 to 
999,900,000. 
REGNn 
n
 = 0 to 9 
nnnn 
ACCUMULATED MOTOR STARTS
— Displays the 
accumulated motor starts in the 1
st
 10% of motor span since 
it was last reset.  See  
Regions of Motor Travel (page 62). Multiply displayed value 
times 10
to get actual value.  Range is 0 to 999,900,000. 
TOTDEG 
nnnn 
TOTAL DEGREES OF MOTOR TRAVEL
 Displays the 
total number of degrees of motor travel since it was last 
reset. Multiply displayed value times 10
to get actual value.  
Range is 0 to 999,900,000.