Honeywell commercial programmable t7350 Manuel D’Utilisation

Page de 44
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
15
63-4368
General Considerations
Table
 
lists wiring types, sizes and distances for the T7350 
and Excel 10 products. The T7350 terminal strip accepts 18 
through 22 AWG (0.82 to 0.34 sq. mm) wire.
Table 8. Field Wiring Reference.
NOTE: 1. The X, RH and RC terminals will accept 14 to 22 AWG. 14 and 16 AWG should be avoided since the stiff cable 
interferes with the cover to subbase installation.
Wire Function
 Recommended Wire 
Size (Minimum)
Specification or 
Requirement
Honeywell Part 
Number
 Distance (Maximum)
Digital Outputs:
W Y G AUX X
18 AWG (0.82 sq mm)
five wire cable bundle.
Standard thermostat 
wire.
AK3726
1000 feet.
Modulating Outputs:
MX MH MC
18 AWG (0.82 sq mm)
1 pair per output.
AK3757C, AK3744C,
AK3741A, AK3702x
1000 feet.
Remote Humidity 
Sensor:
HS HC HP
18 to 22 AWG
(0.82 to 0.34 sq mm)
3 wires.
AK3746C, AK3724, 
AK3703x
500 feet.
Discharge Air 
Temperature Sensor:
AS
18 to 22 AWG
(0.82 to 0.34 sq mm)
1 pair.
AK4606ABE, 
AK4628AWH, 
AK3702x, AK3741A, 
AK3744C, AK3757C
1000 feet.
Outdoor Air 
Temperature Sensor:
OS
18 AWG (0.82 sq mm)
1 pair.
AK3757C, AK3744C, 
AK3741A, AK3702x
500 feet.
Motion Sensor:
M
18 to 22 AWG
(0.82 to 0.34 sq mm)
1 pair.
AK4606ABE, 
AK4628AWH, 
AK3702x, AK3741A, 
AK3744C, AK3757C
1000 feet.
Wall Module 
connections:
T3-T7
18 to 22 AWG
(0.82 to 0.34 sq mm)
Twisted pair wire is 
recommended for wire 
runs longer than 100 
ft. The number of pairs 
depends on the model 
and functions 
selected.
AK4606ABE, 
AK4628AWH, 
AK3702x, AK3741A, 
AK3744C, AK3757C, 
AK3726
1000 feet.
Power Wiring to:
X RH RC
18 to 14
1
 AWG
(0.82 to 2.0 sq mm)
use heavier wire for 
longer runs.
NEC Class II,
140°F (60°C) rating.
AK3702x, AK3741A, 
AK3744C, AK3757C, 
AK3712x, AK3754
Limited by line-loss 
effects on power 
consumption.
L
ON
W
ORKS®
 Bus
(Non-Plenum).
22 AWG
(0.34 sq mm)
Nema Level IV 
U.L. Type CMR 
Twisted pair stranded 
conductor, 
nonshielded.
AK3798 (1 pair)
Refer to E-bus Wiring 
Guidelines Users 
Guide 74-2865 for 
maximum length and 
generic cable 
specifications.
L
ON
W
ORKS®
 Bus
(Plenum Rated).
22 AWG
(0.34 sq mm)
Nema Level IV 
U.L. Type CMP 
Twisted pair stranded 
conductor, 
nonshielded.
AK3797 (1 pair)