Honeywell commercial programmable t7350 Manuel D’Utilisation

Page de 44
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
25
63-4368
APPENDIX D - NETWORK ACCESS TO LOCAL SENSOR DATA
APPENDIX E - SCHEDULING 
NETWORK DEVICES
A T7350H can be used to time schedule the following 
Honeywell controllers:
• Another T7350H.
• T7300/Q7300.
• XL15C application objects (Control loops/StartStop loops).
• XL10 controllers.
A single T7350 can be configured to schedule all (up to 119) 
of the compatible controllers connected to the same network. 
This is accomplished by a one to many binding from the 
source T7350 to the destination controller or object.
T7350.nvoOccSchedule > XL10.nviOccSchedule.
L
ON
S
PEC
™ automatically implements these NV bindings 
based on the selection of Unscheduled Objects (XL10(s), 
Q7300(s), T7300H(s) and XL15cAP(s) located on the 
L
ON
S
PEC
™ T7350 Scheduling Screen.
APPENDIX F - NETWORK MASTER 
CLOCK
A T7350H can be used as the network time master for the 
following network connected Honeywell controllers:
• Another T7350H.
• T7300/Q7300.
• XL15A.
This is accomplished by a one to many binding from the 
source T7350H to the destination controller. The following is 
an example NV binding of one T7350H as a time master to 
another.
T7350H.nvoTime > T7350H.nviTimeSet
L
ON
S
PEC
™ automatically implements these NV bindings 
based on the selection of Network Time Master check box on 
the T7350 General configuration screen. The Day Light 
Saving Start and Stop Month on all time master recipients 
should be configured to None (invalid). This prevents 
erroneous time changes during temporary network outages.
Table 17. T7350H Reports Local Sensor Data.
The T7350H reports local sensor data using the following output network variables.
Nv Name
LonSpec Reference 
Name
Description
nvoDischAirTemp Discharge Temperature 
Out
The current discharge air temperature. The sensor value source is configured 
by nciConfig.dischAirSensor. A value of 327.67 means the sensor is not 
functioning correctly or is out of range.
327.67: Power up value
nvoOccSensor
Occupancy Sensor Out
Status of occupancy sensor 
0: OC_OCCUPIED 
1: OC_UNOCCUPIED
-1: OC_NUL (not configured and power up value)
nvoOutdoorTemp Outdoor Temperature Out
The current outdoor temperature. The sensor value source is specified by 
nciConfig.oDAirSensor. A value of 327.67 means the sensor is not functioning 
correctly or is out of range.
327.67: Power up value
nvoSpaceRH
Space Humidity Out
The current space humidity. The sensor value source is specified by 
nciConfig.humiditySensor. A value of 163.84 means the sensor is not 
functioning correctly or is out of range.
163.84: Power up value
nvoSpaceTemp
Space Temperature Out
The current space temperature. The sensor value source is specified by 
nciConfig.spaceSensor. A value 327.67 means the sensor is not functioning 
correctly or is out of range.
327.67: power up value