T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
33
63-4368
S7760 - Command Display
A network connected Command display can be configured (by 
LonSpec) to implement the following T7350H functions:
View and Modify Schedules:
• Occupied, Unoccupied and Standby setpoints
1
• weekly schedule 
• holiday schedule
NOTE: If a T7350H is connected to a wall module with set-
point adjustment, the user will not be allowed to 
change occupied setpoints through Command Dis-
play.
Command manual occupancy, Annunciate T7350H alarms, 
Monitor T7350H data:
• Room Temperature
• Active Room Temperature SetPoint
• Occupancy Status
• Operating Mode
• Discharge Air Temperature
• Space Humidity
• Outdoor Temperature
• Heat Stages Active
• Cool Stages Active
• Heat Modulating Output Position
• Cool Modulating Output Position
• Bypass Minutes Remaining
• Auxiliary Relay Status
• Fan Status
XL15C
Application Object
Application Input
Source T7350H
Network Variable
Network Variable Field
nvoAlarmStatus
InvalidSubBaseType
nvoError
errLoclSpaceSensr
nvoError
ErrRemtSpaceSensr
nvoError
ErrNetSpaceSensr
nvoError
ErrLoclHumSensr
nvoError
ErrRemtHumSensr
nvoError
errNetHumSensr
nvoError
ErrRemtOdSensr
nvoError
ErrNetOdSensr
nvoError
ErrRemtSetPt
nvoError
ErrDischSensr
nvoError
errIOConfig
nvoError
errSubBaseType
nvoError
errSubBaseVerMisMatch
nvoError
errNviSpaceTemp
nvoError
errNviOccSchedule
nvoError
errNviOccSensor
nvoError
errnviApplicMode
nvoError
errnviOutdoorTemp
nvoError
errnviSpaceRH
nvoError
errNviBypass
nvoError
errNviDLCShed
nvoData2
RelayHeat3
nvoData2
RelayCool3
nvoData2
RelayHeat2
nvoData2
RelayCool2
nvoData2
RelayAux
nvoData2
RelayHeat1
nvoData2
RelayCool1
nvoData2
RelayFan
nvoData2
dehumidActive
Table 20. Network Connections to XL15C AP Inputs. (Continued)
T7350H Network Variable Outputs can be used as inputs to XL15C application objects.