Honeywell commercial programmable t7350 Manuel D’Utilisation

Page de 44
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
5
63-4368
Network Variables—A class of variables defined in Neuron C 
that allows communication over the L
ON
W
ORKS®
 network to 
other nodes on the network. An output network variable in one 
node can be bound to a corresponding input network 
variable(s) in other node(s). Changing the value of the output 
network variable in one node causes the new value to be 
automatically communicated to the bound input network 
variable(s) in other node(s). When an input network variable is 
updated, a nv_update_occurs and the event is posted at the 
receiving node(s) so that the application program can take 
action based on the change. A network management node 
(for example XL15A or XL15C) that explicitly reads and/or 
writes the network variable can also poll network variables. 
Network variables can contain one data field (one or two 
bytes) or multiple data fields (a structure).
Neuron—Refers to the Echelon
®
 semiconductor device which 
implements the L
ON
W
ORKS®
 protocol on a network connected 
device such as the T7350H Honeywell controller.
Node—A device implementing layers one through six of the 
LonTalk
®
 protocol including a Neuron
®
 Chip, transceiver, 
memory, and support hardware.
Notebook PC—Portable personal computer.
PDA—Personal Digital Assistant. In the case of the T7350 
product this is a hand held electronic device operating with the 
Palm OS. A Honeywell provided PDA application program is 
used to configure the T7350 thermostat using a direct RS232 
connection. Before purchasing a PDA, check the latest 
Configuration software release note for a list of qualified PDA 
models. Network connected T7350H models can be 
configured without a PDA using L
ON
S
PEC
™.
Programmable Controller—A controller that has a variable 
number of control loops of different types and is user 
programmed to execute an application. The user can select 
the number and type of control loops. The user also has the 
capability of generating new types of control loops. Some 
examples of Honeywell programmable controllers include the 
XL15A and XL15B.
Recovery Mode or Recovery Period—The time in 
unoccupied periods when the temperature control is adjusting 
the control setpoint so that the space temperature reaches the 
occupied setpoint when the schedule change occurs.
RIO—Excel 10 Remote Input/Output device.
RTC—Real Time Clock.
Schedule—The structure that defines the occupancy states 
and the time of the changes between these states. In the case 
of the T7350, schedules are organized around a eight day 
weekly structure including an extra day for designated 
holidays. Holidays are scheduled by yearly calendar events.
SGPU—Significant Event Notification and Guaranteed 
Periodic Update.
SGPUC—Significant Event Notification and Guaranteed 
Periodic Update with Change Field.
SLTA—Serial LonTalk
®
 Adapter. Adapts the transformer 
coupled LonTalk
®
 messages to the RS-232 Serial Port.
SNVT—Standard Network Variable Type.
SCPT—Standard Configuration Parameter Type.
XL15A—W7760A Honeywell building level controller.
XL15B—W7760B Honeywell building level controller.
XL15C—W7760C Honeywell plant level controller.
Performance Specifications
IMPORTANT
The specifications given in this publication do not 
include normal manufacturing tolerances. Therefore, 
this unit might not exactly match listed specifications. 
This product is tested and calibrated under closely 
controlled conditions; minor performance differences 
can be expected if those conditions are changed.
Models: See Table 4.
Dimensions: See Fig. 2.
Finish (color): Trident White.
Batteries: No batteries required.
Table 4. T7350 Thermostat Features.
a
All models are down-selectable and can be configured to control fewer stages than the maximum allowed.
b
Heat pump applications for these models have a maximum of two heat stages and two cool stages.
c
One extra stage (of either heat or cool) can be configured using the auxiliary relay.
Model
Applications
Maximum Stages
a
Features
Auxiliary
Relay
L
ON
W
ORKS
® 
Capability?
Heat
Cool
T7350H1009 Conventional
 or
 Heat Pump
3 (2)
b
3 (4)
b
Humidity, Occupancy, 
Outdoor, Discharge Air Capability
Isolated 
Normally 
Open
Yes
T7350H1017 Modulating
2 modulating, 2
c
 relay Humidity, Occupancy, 
Outdoor, Discharge Air Capability, 
4-20 mA output (2-10 Vdc with 500 ohm resistor)
Yes