Radiance Direct Vent Gas Heater
20012697
�����
��������
����
Figure 51
Left Cross 
Log
Rear Log
Right Cross Log
Front Right Log
Front Left Log
Ember Bed
LG490
Connect the Gas Supply Line
Check the Rating Plate attached by a steel cable to the 
firebox, to confirm that you have the appropriate firebox 
for the type of fuel to be used. The Radiance may be 
converted from one gas to another using the appropri-
ate Fuel Conversion Kit listed on Page 45.
In the U.S.; Gas connection should be made in ac-
cordance with current National Fuel Gas Code, ANSI 
Z223.1/NFPA 54. Since some municipalities have 
additional local codes, be sure to consult your local 
authority.
In Canada; consult the local authority and CSA-B149.1 
installation code.
Always check for gas leaks with a mild 
soap and water solution. Do not use an 
open flame for leak testing.
Light the pilot according to the directions on Page 30, 
before going to the next step.
This appliance should only be connected 
by a qualified gas technician. Test to 
confirm manifold pressures as specified 
below.
The Radiance Heater and its individual shutoff 
valve must be disconnected from the gas supply 
piping during any pressure testing of that system 
at test pressures in excess of 1/2 psig (3.5 kPa).
The Radiance Heater must be isolated from the 
gas supply piping system by closing its indi-
vidual manual shutoff valve during any pressure 
testing of the gas supply piping system at test 
pressure equal to or less than 1/2 psig.
There must be a gas shutoff between the stove 
and the supply.
In order to connect Natural Gas, use a fitting 
with 1/2” NPT on the valve side and 1/2” natural 
gas supply line with an input of 38,000 BTUs at a 
manifold pressure of 3.5” between minimum inlet 
supply of 5.5” w.c. and maximum of 14.0” w.c. 
In order to connect Propane, use a fitting with 1/2” 
NPT on the valve side and 1/2” propane gas sup-
ply line with an input of 36,000 BTUs at a manifold 
pressure of 10.0” between a minimum inlet supply 
of 11.0” w.c. and maximum of 14.0” w.c.
CAUTION
Burner Information
The appliance must only use the gas specified on the 
rating plate, unless converted using a Vermont Castings 
Fuel Conversion Kit. To convert from Natural Gas to LP 
use Kit 20012729 or 20012900. To convert from LP to 
Natural Gas use Kit 20012899 or 20012902. 
Conversion instructions are provided with each kit and 
beginning on Page 36 in this manual.