Tecnoware EVO DSP PLUS MM 1.2 FGCEVDP1202MM Fascicule
Codes de produits
FGCEVDP1202MM
L
’A
Z
IE
N
D
A
ON LINE MM
UPS EVO DSP PLUS MM
1.2-2.4-3.6
Accessories
Model Code
Bypass Box for UPS MM from 1 KVA to 3.6 KVA
FGCBYPIEC
Dry Contact for Evo Dsp MM and Evo Dsp Plus MM
FGCEVODSDRY3
SNMP for Evo Dsp MM and Evo Dsp Plus MM
FGCNETAG7
IEC320 C20/M connector to wire
ESNIEC60320C20
© 2014 Tecnoware Power Systems. I dati tecnici possono essere variati senza preavviso.
Available on request with input/output nominal voltage 110Vac or 120Vac and with input plug and output sockets for specifi c country.
Specifi cations
40
60
80
100
0
6
9
12
5° C (41° F)
25° C (77° F)
30° C (88° F)
40° C (104° F)
25° C (77° F)
30° C (88° F)
40° C (104° F)
UPS (with batteries) storage
Battery capacity (%)
Storage (months)
It is necessary to
recharge the batteries
for a minimum
of 24 hours.
recharge the batteries
for a minimum
of 24 hours.
Attention: batteries
may not be recoverable
even when subjected
to charging.
may not be recoverable
even when subjected
to charging.
3
15
18
21
24
27
30
UPS Battery life in operating conditions
The higher is the temperature of the environment in which the
UPS works, the shorter is the battery life.
UPS works, the shorter is the battery life.
0
1
4
5
20
0
30
40
50
6
Battery life (years)
Temperature (C°)
25
35
45
3
2
1,5
UPS Model
EVO DSP PLUS MM 1.2
EVO DSP PLUS MM 2.4
EVO DSP PLUS MM 3.6
Code
FGCEVDP1202MM FGCEVDP2402MM
FGCEVDP3602MM
Nominal power
1.200 VA
2.400 VA
3.600 VA
Active power
840 W
1.680 W
2.520 W
Power factor
0,7
Technology
On-Line Double Conversion transformerless (VFI-SS-111)
Cooling
Fan
cooling
Audible noise
< 45 dBA at 1 m
Dimension (UPS) WxHxD
15x22x40 cm
19x32x42 cm
Dimension (with packing) WxHxD
23x33x47 cm
33x46x56 cm
Weight
12 Kg
18 Kg
30 Kg
Equipped with
1 power cable
2 output cables (IEC type)
Input
Number of phases
Number of phases
1Ph+N
Nominal voltage
208Vac/220Vac/230Vac/240Vac
Input voltage range
160Vac-300Vac from 50% to 100% load, 110Vac-300Vac up to 50% load
Nominal frequency
50/60 Hz (selectable)
Input frequency range (On-Line mode)
±7%
Input power factor
0,99
Output
Number of phases
Number of phases
1Ph+N
Nominal voltage
208Vac/220Vac/230Vac/240Vac
Static voltage Regulation at %100
±2%
linear load (On-Line and battery mode)
Voltage THD at rated linear load
<3% (linear load), <6% (non-linear load)
Crest factor
3:1
Frequency
50/60 Hz (selectable)
Free running frequency
±0,2 Hz
Inverter waveform
Sinewave
Overload capability
100-110% only audible warning, 110-130% for 30 sec, >130% for 100 ms
Effi ciency
>92% (line/battery mode), >98% (ECO mode)
Transfer time
0 ms (On-Line)
Outlets
4 (IEC 320 C13 type)
6 (IEC 320 C13 type) + 1 (IEC 320 C19 type)
Bypass
Number of phases
1ph+N
Nominal voltage
208Vac/220Vac/230Vac/240Vac
Voltage range
Low threshold 170Vac-220Vac (selectable) - High threshold 230Vac-264Vac (selectable)
Eco Mode
Voltage range
Voltage range
Low threshold from -7 to -24Vac (selectable) - High threshold from +7 to +24 Vac (selectable)
Input frequency range (50Hz nominal frequency)
47-53 Hz
Input frequency range (60Hz nominal frequency)
57-63 Hz
Battery
Type
Type
Lead acid, sealed, maintenance free
Batteries number
2 (internal)
4 (internal)
6 (internal)
Battery charge time (typical)
6-8 hours
Nominal battery voltage
24Vdc
48Vdc
72Vdc
Battery specifi cation
12Vdc - 9Ah
Backup time (Typical)
10 min
Interfacing
Interface (communication port)
USB (card slot)
Dry contact interface
Yes (optional
replacing USB)
Software
TecnoManager downloadable free from
www.tecnoware.com (compatible with WINDOWS, UNIX, LINUX, ecc.)
SNMP interface
SNMP internal module (compatible with WINDOWS, UNIX, LINUX, ecc.) - optional
Phone/modem line protection
RJ11/RJ45 plug
Environmental specifi cation
Storage temperature
Storage temperature
From -15 to 40 °C (for Battery Box with battery inside, see “Storage of batteries in UPS and Battery Box” graphic)
Working temperature
From 0 to 40 °C (recommended from 20 to 25 °C, for a correct battery use see “Battery life in service” graphic)
Humidity
< 95% without condensation
Maximum altitude
3000 m
IP protection
IP20
Certifi cations
CE (Standards: Low Voltage Directive IEC EN 62040-1; EMC Directive IEC EN 62040-2; classifi cation IEC EN 62040-3)
Warranty
Standard
24 months electronic parts and 12 months batteries
Extensions
Optional
www.tecnoware.com