International English 3. COMMISSIONING
34
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
3.1.4
Commissioning with the Advanced Operator Panel (AOP)
The Advanced Operator Panel (AOP) is available as an option.
Its advanced features include the following:
Its advanced features include the following:
Multilingual clear text display
Upload/download of multiple parameter sets
Programmable
via
PC
Multidrop capability to drive up to 30 MICROMASTER 4’s
Please refer to the AOP Manual for details or contact your
local Siemens sales office for assistance.
local Siemens sales office for assistance.
3.2 General
operation
For a full description of standard and extended parameters, please refer to Section 6.
3.2.1 General
1. The inverter does not have a main power switch and is live when the mains supply is
connected. It waits, with the output disabled, until the RUN button is pressed or for
the presence of a digital ON signal at terminal 5 (rotate right).
the presence of a digital ON signal at terminal 5 (rotate right).
2. If a BOP or an AOP is fitted and the output frequency is selected to be displayed
(P0005 = 21) the corresponding setpoint is displayed approximately every 1.0
seconds while the inverter is stopped.
seconds while the inverter is stopped.
3. The inverter is programmed at the factory for standard applications on Siemens four-
pole standard motors that have the same power rating as the inverters. When using
other motors it is necessary to enter the specifications from the motor's rating plate.
See figure 3-5 for details on how to read motor data.
other motors it is necessary to enter the specifications from the motor's rating plate.
See figure 3-5 for details on how to read motor data.
Notes
♦ Changing motor parameters is not possible unless P0010 = 1.
♦ You must set P0010 back to 0 in order to initiate run.
3.2.2
Basic operation with SDP
Prerequisites
The terminals are connected like shown in Figure 3-2
The terminals are connected like shown in Figure 3-2
♦ Start and stop the motor via switch between terminals 5 and 8
♦ Reverse the motor via switch between terminals 6 and 8
♦ Control the motor speed by the potentiometer, connected to the terminals 1 to 4
RUNNING
P000
I = 4.8
fn
fl
p
v
F=
50.0
HZ
RPM=1500
V=400v
Jog
0
1
P
Fn
menu