Commissioning (software)
4.6 Using drive-related I/Os by SIMOTION
D410
Commissioning Manual, 08/2008 Edition
Commissioning Manual, 08/2008 Edition
99
Figure 4-27 Example: Interconnection of the onboard DI in the PROFIBUS send direction
Note
A warning message is not output if you interconnect more PSDs than were set in the
A warning message is not output if you interconnect more PSDs than were set in the
additional PSDs. Note that a SERVO drive object supports a maximum of 16 PSD
setpoints and 19 PSD actual values. Each VECTOR drive object supports a maximum of
32 PSD setpoints.