Step 5: Wire the Power Supply
ION8800 meter power supply connections are found on the Essailec
connector.
connector.
Single Phase Power Supply
Step 6: Power Up the Meter
D
ANGER
Before you apply power to the meter, ensure that ground is securely
connected and that the supply voltage is within the allowed range of the
meter’s power supply.
Step 7: Set Up the Meter Using the Front Panel
The following Setup screens are available for meter configuration via the
front panel:
front panel:
The following example shows Volts Mode setup using the meter front panel.
Fuse for N/-
terminal required if
neutral is
ungrounded.
Rated Inputs
85 - 240 VAC ±10%
(47 - 63 Hz)
110 - 270 VDC ±10%
Rating
Installation category II (local), Pollution degree 2
Dielectric Withstand
2,000 VAC RMS for 60s (50Hz)
Max. Burden
9 W (20 VA) for base unit without comm module
Ride-through
Min: 120 ms (6 cycles @ 50 Hz)
Typical: 0.5 - 5 s (depending on input voltage and
configuration)
Typical: 0.5 - 5 s (depending on input voltage and
configuration)
BASIC SETUP
DEMAND SETUP
COM1 SETUP
COM2 SETUP
COM3 SETUP
COM4 SETUP
NETWORK SETUP
FORMAT SETUP
DISPLAY SETUP
SECURITY SETUP
Press
ALT
/
ENTER
and
hold for 3 seconds
to
enter Setup Mode
from Display Mode.
Use arrow buttons to
move up and down in
list. Press
ALT
/
ENTER
to
select Basic Setup.
Use arrow buttons to
move up and down in
list. Press
ALT
/
ENTER
to
select Volts Mode.
Use arrow buttons to
move up and down in
list. Press
ALT
/
ENTER
to
select
4
W
-
WYE
.
Press and hold
Press
Press
Press
Press