Honeywell Work Light DR4300 Manuel D’Utilisation

Page de 262
DR4300 Circular Chart Recorder 
88 
DR4300 Circular Chart Recorder Product Manual 
12/03 
Lower Display 
Prompt 
Upper Display  
Range of Setting  
or Selection 
Parameter  
Definition 
BRNOUT 
 
 
 
 
 
 
 
 
NONE [factory setting] 
UP 
 
 
DOWN 
BURNOUT PROTECTION (INPUT FAILURE)
 provides most input 
types with upscale or downscale protection if the input fails. Note 
that if the input fails, error message “INP FL” will be on the lower 
display. 
ATTENTION
 Refer to Subsection 4.5 for information about the 
interaction of the value of this parameter and the setting of switch 2 
on SW6. 
  
NO BURNOUT
—Failsafe output applied for failed input.  
UPSCALE BURNOUT
 will make the indicated PV signal go to 
overrange value when input fails. Control algorithm will use 
overrange value when calculating output. 
DOWNSCALE BURNOUT
 will make the indicated PV signal go to 
underrange value when input fails. Control algorithm will use 
underrange value when calculating output. 
 
NOTE: For recorders with the FM Limit Approved Option the INPUT configuration does not provide a 
burnout selection. However, if a HI limit is configured and the input opens, the input reading will go 
Upscale and the lower display will alternate between: INP#, Limit, and INP FL. 
If a LO limit is configured and the input opens, the input reading will go down scale and the lower display 
will alternate between: INP#, Limit, and INP FL.