Heatcraft Refrigeration Products Condensing Units H-IM-CU Manuel D’Utilisation

Page de 24
1
System Balancing - Compressor Superheat
IMPORTANT:
In order to obtain the maximum capacity from a system, and to ensure 
trouble-free operation, it is necessary to balance each and every system.
This is extremely important with any refrigeration system.
The critical value which must be checked is suction superheat.
Suction superheat should be checked at the compressor as follows:
Measure the suction pressure at the suction service valve of the  
 
 
compressor  and  determine  the  saturation  temperature  corresponding  
 
to this pressure from a  “Temperature-Pressure” chart.
Measure the suction temperature of the suction line about one  
 
 
foot back from the compressor using an accurate thermometer.
Subtract the saturated temperature from the actual  
 
 
 
suction line temperature. The difference is superheat.
Too low a suction superheat can result in liquid being returned to the 
compressor. This will cause dilution of the oil and eventual failure of the 
bearings and rings or in the extreme case, valve failure.
Too high a suction superheat will result in excessive discharge temperatures 
which cause a break down of the oil and results in piston ring wear, piston 
and cylinder wall damage.  
It should also be remembered that the system capacity decreases as the 
suction superheat increases.  For maximum system capacity, suction 
superheat should be kept as low as is practical. Copeland mandates a 
minimum superheat of 20˚F at the compressor.  We recommend that the 
superheat at the compressor be between 20˚F and 30˚F.
If adjustments to the suction superheat need to be made, the expansion 
valve at the evaporator should be adjusted.
1.
2.
3.
Operational Check Out
After the system has been charged and has operated for at least two hours at 
normal operating conditions without any indication of malfunction, it should 
be allowed to operate overnight on automatic controls.  Then a thorough 
recheck of the entire system operation should be made as follows:
Check compressor discharge and suction pressures.    
 
 
If not within system design limits, determine why and   
 
 
take corrective action.
Check liquid line sight glass and expansion valve operation. If    
 
there are indications that more refrigerant is required, leak test    
 
all connections and system components and repair any  
 
 
leaks before adding refrigerant.  
Observe oil level in compressor crankcase sight glass.  Add oil as   
 
necessary to bring level to bottom 1/4 of the sight glass.  
Thermostatic expansion valves must be checked  
 
 
 
for proper superheat settings. Feeler bulbs must be    
 
 
in positive contact with the suction line and should    
 
 
be insulated. Valves set at high superheat will lower    
 
 
refrigeration capacity.  Low superheat promotes  
 
 
 
liquid slugging and compressor bearing washout.
Using suitable instruments, carefully check line voltage and  
 
 
amperage at the compressor terminals. Voltage must be within    
 
10% of that indicated on the condensing unit nameplate.  If high  
 
or low voltage is indicated, notify the power company.   
 
 
If amperage draw is excessive, immediately determine the cause   
 
and take corrective action.  On three phase motor compressors,    
 
check to see that a balanced load is drawn  
 
by each phase.  
The maximum approved settings for high pressure controls on    
 
our air cooled condensing equipment is 425 psig.  On air cooled    
 
systems, check as follows:   
 
Disconnect the fan motors or block the condenser inlet air.  Watch  
 
high pressure gauge for cutout point.  Recheck all safety and  
 
 
operating controls for proper operation and adjust if necessary.  
Check defrost controls for initiation and termination settings, and  
 
length of defrost period.  Set fail safe at length of defrost + 25%. 
 
Example:   
20 minute defrost  + 5 minutes 
 
 
 
=   25 minute fail safe  
Check drain pan for proper drainage.
Check winter head pressure controls for pressure setting.
Check crankcase heater operation if used.
Install instruction card and control system diagram for  
 
 
use of building manager or owner.
a)
b)
c)
d)
e)
f)
g)
h)
i)
j)
k)
NOTE:
All adjustable controls and valves must be field adjusted to meet desired 
operation. There are no factory preset controls or valve adjustments. This 
includes low pressure, high pressure, adjustable head pressure systems 
and expansion valves.
Table 9. Recommended Low Pressure Control Settings for Outdoor Air Cooled Condensing Units
*Minimum
Temp. ˚F
R-22
R-0A/R-507
Cut-In PSI
Cut-Out PSI
Cut-In PSI
Cut-Out PSI
50
70
20
90
35
40
55
20
70
35
30
40
20
55
35
10
30
10
45
25
0
15
0
25
7
-10
15
0
20
1
-20
10
0
12
1
-30
6
0
8
1"Hg.
* Minimum ambient or box temperature anticipated, high pressure control setting: R-22, 360 PSI; R-404A, R-507, 400 PSI
* The standard preset low pressure switch used for pumpdown is set for 15 PSI cut in / 4 PSI cut out and is a good setting for most pumpdown systems
* ZB Scroll compressors should be set for 25 PSI cut in / 17 PSI cut out (R-404A / R-507)