APC AP9810 Manuel D’Utilisation
8
Dry Contact I/O SmartSlot Card
Dip switches: input and outputs
The table below lists the four possible configurations, with their corresponding
inputs and outputs.
inputs and outputs.
* With this setup (the factory default), the Configuration Utility is used automatically.
Configuration 1
Configuration 2
Configuration 3
Configuration 4*
OFF-OFF-OFF-ON
ON-OFF-OFF-ON
OFF-ON-OFF-ON
ON-ON-OFF-ON
Inputs
Device Actions
1
Turn the UPS on.
See
Configuration
Utility
Configuration
Utility
2
Turn the UPS off.
Turn the UPS off
safely.
safely.
3
Start UPS self-test.
4
Shut down the UPS
when on battery
except for self-test or
runtime calibration.
when on battery
except for self-test or
runtime calibration.
Put the UPS in
bypass, if bypass is
available on the
UPS.
bypass, if bypass is
available on the
UPS.
Shut down the UPS
when on battery
except for self-test or
runtime calibration.
when on battery
except for self-test or
runtime calibration.
Outputs
Device State
1
The UPS is on-battery (e.g., during a power failure, self-test, or
runtime calibration).
runtime calibration).
See
Configuration
Utility
Configuration
Utility
2
The UPS has a low battery.
3
The protected load is not receiving power from the UPS or
communication between the UPS and the Relay I/O Card has been
lost.
4
Replace the UPS battery.
UPS commanded to
turn on
(echo of Input 1).
5
The UPS is
overloaded.
The UPS is in bypass
by selection from
software, front panel,
or rear panel.
UPS commanded to
turn off gracefully
(echo of Input 2).
6
Any UPS fault or
self-test failure.
Any UPS fault, self-
test failure, or
overload.
Any UPS fault, self-
test failure, overload,
or replace battery
test failure, overload,
or replace battery