Motor Setup 
 215 
Current-Loop Tuning: Ixx61, Ixx62, Ixx76 
The current-loop tuning is done as in any Turbo PMAC digital current loop setup. The PMACTuningPro2 
automatic  or  interactive  utility  can  be  used  to  fine-tune  the  Current-Loop.  An  acceptable  Current-Loop 
step response would look like: 
 
 
 
 
Note 
Current-Loop  Natural  Frequencies  in  the  range  of  200-500  Hz  are 
good enough for most applications. Tuning the current loop too tightly 
(Natural  Frequency  >  800Hz)  can  have  deteriorating  effects  on  the 
position loop tuning.   
 
Position-
Loop PID Tuning: Ixx30…Ixx39 
Since no “real” encoder is used, the position-loop PID gains are pre-calculated:  
I430=1024 I431=0 I432=85 I433=1024 I434=1 I435..439=0