Turbo PMAC/PMAC2 Software Reference
 
Turbo PMAC On-line Command Specification 
 358 
M{constant}->TWR:{address} 
Function: 
Resolver Thumbwheel-Multiplexer M-Variable Definition 
Scope: 
Global 
Syntax: 
M{constant}[..{constant}]->TWR[:]{multiplex address}, 
{offset} 
where: 
 
{constant} is an integer from 0 to 8191 representing the number of the M-variable; 
 
the optional second {constant} must be at least as great as the first {constant} -- it represents 
the number of the end of the range; 
 
{multiplex address} is an integer constant, divisible by 2, in the range 0 to 254, representing 
the address in the multiplexing scheme of the Acc-8D Option 7 resolver-to-digital converter board on 
the thumbwheel multiplexer port, as determined by the DIP switch settings on the board 
 
{offset} is an integer constant from 0 to 7, representing the location of the device at the specified 
multiplexer address, as determined by  in the buffer on the Acc-8D Option 7 and the actual pins to 
which the device was wired. 
This command causes Turbo PMAC to define the specified M-variable or range of M-variables to point to 
a 12-bit word from a resolver-to-digital (R/D) converter or similar device serially multiplexed on the 
thumbwheel port on an Acc-8D Option 7 or compatible board. 
The address on the multiplex port specified here must match the address set by the DIP switches on board 
the Acc-8D Option 7.  The Acc-8D Option 7 manual contains a table listing all of the possibilities.   
One of the DIP switches on the Acc-8D Option 7 board determines whether the R/D converters on board 
have offset values of 0 to 3 or 4 to 7.  The {offset} specifier must match this DIP switch setting and 
the number of the R/D device on the board. 
This is a read-only M-variable format.  Use of this variable in an on-line query command or a program 
statement will cause Turbo PMAC to clock in 12 bits of unsigned data (range 0 to 4095) from the 
specified device through the multiplexer port. 
Note:  
It is not necessary to use an M-variable to access an R/D converter for actual servo 
or phasing feedback purposes.  I-variables (Ixx10, Ixx81, Ixx98, Ixx99) are used 
for that purpose.  However, even if this is the only use of the R/D converter, 
usually it is desirable to assign M-variables to the R/D converters for set-up and 
diagnostic purposes. 
Example: 
M100->TWR:0,0 
M99->TWR:4,5 
See Also: 
M-Variables (Computational Features) 
On-line commands M{constant}M{constant}-> 
 
M{constant}->TWS:{address} 
Resolver-to-Digital Converter Board (Acc-8D Opt-7) Manual 
M{constant}->TWS:{address} 
Function: 
Serial Thumbwheel-Multiplexer M-Variable Definition 
Scope: 
Global 
Syntax: 
M{constant}[..{constant}]->TWS[:]{multiplex address} 
where: 
 
{constant} is an integer from 0 to 8191 representing the number of the M-variable;