8  SPI Enable/Disable & Loopback Test 
Range = 0 to 1, Default = 0 
When the expanded service menus are enabled, an additional parameter becomes available on 
this menu. Set this parameter to 
1
  to enable SPI communications. Set it to 
2
  to perform an 
internal self test. Disconnect all communication cables before performing the internal self-
test;
 no loopback cable is needed. 
 
Note: 
To exit the self-test, you’ll need to perform a complete reset: 
reapply power to the control while pressing both the 
CLEAR
 UP 
key and DOWN key together simultaneously. All parameters 
reset to the factory defaults so make a note of the parameter 
settings
 you want to retain. 
 
 
If the Series One Plus screen alternates displays of the numbers 
85
  and 
170
 , a self test is successful. This condition continues 
until you do a complete reset. During the test, the number 
85
 
continuously transmits out the port. When the controller receives 
an 
85
, it echoes a 
170
Menu 
9 SPI 
Address 
Range = 32 to 254, Default = 32 
Each auxiliary device on an SPI network must be assigned a unique address to identify it to the 
IMM controlling the network. Do not assign the same address to any two auxiliary 
machines
 on the network, or line contention will occur. 
Menu 
10  SPI Baud Rate 
Range = 300 to 19,200 bps, Default = 4,800 bps 
The baud rate in bits per second (bps) is the data transmission rate. All units on the network 
must be set at the same baud rate. 
In general, this rate should be set to the fastest common 
speed available to the controllers on the network where satisfactory communication occurs.