Honeywell R0512 Manuel D’Utilisation

Page de 86
EXCEL 50/100/500/600/800 
ALARM HANDLING  
 
 
EN2B-0092GE51 R0512 
47 
Alarm 
no. 
alarm text 
English) 
cond. 
code # 
cause/reason 
                                                                                                                               
14 
Return to normal 
79 
Alarm condition control for DI, PD points. 
15 
Hware clock failed 
61 
Error while initializing the system clock. 
16 
Battery low 
17 
Battery voltage too low or battery not existent. 
17 
Battery status OK 
87 
Battery voltage back to normal again (alarm occurs only after alarm message "Battery 
low"). 
18 
Wrong Module ID 
71 
An invalid module ID is read (error on internal I/O or defect module or the module has an 
as-yet unspecified module ID). 
19 
Too Many DO 
Module 
60 
Too many modules of the same type (XF521, XF522, ...). 
20 
Contr. w/o Flash 
81 
Error occurred when burning the Flash EPROM. 
21 
FLASH Mem Full 
82 
Not enough Flash memory space to save application. 
22 
Link Point Alarm 
Xlink alarm. 
23 
Link Comm Down 
Xlink alarm. 
24 
No characteristic 
57 
The application part "Characteristics" is defect. 
25 
RCL Submod 
missing 
RACL sub-module missing. 
26 
Download SSI Now  - 
Xlink alarm. 
27 
Download CPU 
Now 
Xlink alarm. 
28 
RACL inconsistent  29 
Incompatible version numbers of RACL program and RACL parameter files and/or 
datapoint description. 
29 
Nested 
submodules! 
30 
RACL program contains errors (MCAL from submodule). 
30 
alarm message 
158 
Alarm not used. 
31 
RACL undef. 
OpCode 
32 
RACL program contains errors (undefined Operation code). 
32 
RACL program 
fault 
33 
RACL program contains errors (Checksum changed). 
33 
Unknown datapoint  34 
1) During RACL run, datapoint contains errors or point is locked. 
2) An unrecognized (missing) characteristic in the datapoint editor has been used. 
Check if the default file set of the controller is different from the set used in CARE. 
34 
SSI Points Active 
 
Xlink alarm. 
35 
Invalid operation 
36 
Non-valid arithmetical operation during RACL performance (e.g. division by zero or RACL 
statements LN with input value 1.0 ). 
36 
RACL overflow 
37 
Arithmetic overflow at RACL performance "+infinite". 
37 
RACL neg. 
overflow 
38 
Arithmetic underflow at RACL performance "-infinite". 
38 
RACL inval. 
OpCode 
39 
RACL program contains errors (invalid Operation Code). 
39 
Z-Reg. index error 
40 
Access to non-existing Z register (e.g.: RACL statements ISTO and IRCL). 
40 
Invalid Y-Register 
41 
Too many statements (exits) in one column. 
41 
Invalid P-Register 
42 
Attempt to use non-existent P register. 
42 
Invalid T-Register 
43 
Attempt to use non-existent T register. 
43 
Invalid Z-Register 
44 
Attempt to use non-existent Z register. 
44 
SSI Interface Up 
Xlink alarm. 
45 
No parameter file 
RACL parameter file missing. 
46 
No Z file 
RACL Z register file missing. 
47 
No T file 
RACL time register file missing.