Honeywell R0512 Manuel D’Utilisation
EXCEL 50/100/500/600/800
ALARM HANDLING
EN2B-0092GE51 R0512
47
Alarm
no.
no.
alarm text
English)
English)
cond.
code #
code #
cause/reason
14
Return to normal
79
Alarm condition control for DI, PD points.
15
Hware clock failed
61
Error while initializing the system clock.
16
Battery low
17
Battery voltage too low or battery not existent.
17
Battery status OK
87
Battery voltage back to normal again (alarm occurs only after alarm message "Battery
low").
low").
18
Wrong Module ID
71
An invalid module ID is read (error on internal I/O or defect module or the module has an
as-yet unspecified module ID).
as-yet unspecified module ID).
19
Too Many DO
Module
Module
60
Too many modules of the same type (XF521, XF522, ...).
20
Contr. w/o Flash
81
Error occurred when burning the Flash EPROM.
21
FLASH Mem Full
82
Not enough Flash memory space to save application.
22
Link Point Alarm
-
Xlink alarm.
23
Link Comm Down
-
Xlink alarm.
24
No characteristic
57
The application part "Characteristics" is defect.
25
RCL Submod
missing
missing
-
RACL sub-module missing.
26
Download SSI Now -
Xlink alarm.
27
Download CPU
Now
Now
-
Xlink alarm.
28
RACL inconsistent 29
Incompatible version numbers of RACL program and RACL parameter files and/or
datapoint description.
datapoint description.
29
Nested
submodules!
submodules!
30
RACL program contains errors (MCAL from submodule).
30
alarm message
158
158
-
Alarm not used.
31
RACL undef.
OpCode
OpCode
32
RACL program contains errors (undefined Operation code).
32
RACL program
fault
fault
33
RACL program contains errors (Checksum changed).
33
Unknown datapoint 34
1) During RACL run, datapoint contains errors or point is locked.
2) An unrecognized (missing) characteristic in the datapoint editor has been used.
Check if the default file set of the controller is different from the set used in CARE.
34
SSI Points Active
Xlink alarm.
35
Invalid operation
36
Non-valid arithmetical operation during RACL performance (e.g. division by zero or RACL
statements LN with input value 1.0 ).
statements LN with input value 1.0 ).
36
RACL overflow
37
Arithmetic overflow at RACL performance "+infinite".
37
RACL neg.
overflow
overflow
38
Arithmetic underflow at RACL performance "-infinite".
38
RACL inval.
OpCode
OpCode
39
RACL program contains errors (invalid Operation Code).
39
Z-Reg. index error
40
Access to non-existing Z register (e.g.: RACL statements ISTO and IRCL).
40
Invalid Y-Register
41
Too many statements (exits) in one column.
41
Invalid P-Register
42
Attempt to use non-existent P register.
42
Invalid T-Register
43
Attempt to use non-existent T register.
43
Invalid Z-Register
44
Attempt to use non-existent Z register.
44
SSI Interface Up
-
Xlink alarm.
45
No parameter file
-
RACL parameter file missing.
46
No Z file
-
RACL Z register file missing.
47
No T file
-
RACL time register file missing.