Chapter 4: Operation 
35 of 73 
2.  Depress the 
 or 
 button to highlight SETPOINTS and press 
.  If 
passwords were setup (See Section 3-12 for information on the controller 
passwords) the password screen will appear.  
 
Enter the Operator Password by depressing the 
 to move the position of 
the cursor, and then depressing the 
  or 
 button to increment or 
decrement the number.  Once all of the numbers have been entered depress 
the 
 to accept the password. The following screen will appear. 
 
Figure 13 - Operator Setpoints Screen 
3.  Depress 
 to move the cursor to the Leaving Temp line.  Use the 
 or 
 button to increment or decrement the value.  Depress 
 to accept the 
value and move the cursor down one line. 
4.  Adjust the Hi Temp Warning and Hi Temp Fault in the same manner. 
5.  Depress the 
 button twice to return to the main status screen. 
4-6 Alarms 
The controller is setup with multiple alarms, most of them configurable using the Supervisor 
password.  Section 4-5 Controller Setpoints gives a list of alarms that the controller is setup to 
display.  The alarms are broken up into two categories – warnings and faults.  The warning 
notifies the user that the parameter has been exceeded and the chiller is allowed to keep 
operating, but should be monitored to determine the cause of the warning.  The fault notifies 
the user that the parameter has been exceeded and the chiller and pump has been shut down to 
protect the system. 
4-7 Optional 
Communications 
The communications function allows you to monitor and set the parameters by a program 
prepared and running on a host computer connected to the controller.