Sterling 882.93092.00 Manuel D’Utilisation

Page de 73
GP Series Portable Chillers 
Chapter 2: Functional Description 
9 of 73 
•  208-230/3/60, 460/3/60, 575/3/60 volt; 400/3/50 volt 
Refrigeration Features 
•  HFC-410a refrigerant 
•  Electronic hot gas bypass capacity control 
•  High refrigerant pressure cutout switches  
•  Suction and discharge pressure transducers. 
•  High pressure spring actuated relief valve 
•  Multiple refrigeration access ports 
•  Liquid line shut-off ball valves 
•  Filter-dryer 
•  Sight glass 
•  Externally equalized thermal expansion valve 
•  Liquid line solenoid 
•  Compressor crankcase heater 
Controller Features 
•  Off-the-shelf microprocessor-based PID controller with To Process, From Process and 
Set Point readout 
•  Time delay for proof of water flow/pressure (models w/pump only) 
•  Low refrigerant pressure time delay for low ambient start-up on remote air-cooled and 
air-cooled chillers with the variable-speed fan option. 
•  8 line x 20 character display with status, alarm, and service screens 
Other Features 
•  One year labor warranty and one year compressor  warranty 
•  Two year parts warranty 
•  Two year limited controller warranty 
2-4 Safety 
Devices and Interlocks 
Caution!  Protect the system from freezing with glycol 20ºF below the leaving water 
temperature set point. Condensation may form inside the pump tank and dilute 
the mixture, therefore the freezing point should be verified periodically. See 
Figure 6 on page 18 for the correct mixture.  
Crankcase Heater 
All of the chillers are equipped with a compressor crankcase heater. It is wired through the 
control transformer that operates continuously whenever power is applied to the chiller.