KT-MOD-OUT16
KT-400 Expansion Module 16-Output with SPI Cable Install Sheet
 
1. Introduction 
The KT-MOD-OUT16 is a 16 zones output module. It can be 
used for elevator access control (may require additional 
hardware).  
The module supports daisy chaining; you can interconnect up to 
16 KT-MOD-OUT16 modules for a total of 256 external outputs 
per KT-400. You can mix relays and outputs in the same SPI 
group, up to 256 outputs. 
Note 1: The KT-400 SPI port maximum current draw, when the 
12V AUX terminals are not used, is 500 mA. 
Note 2: External power supply (12 VDC, 2 Amps) is required 
when the total current draw exceeds 500mA on the SPI Port. 
Note 3: There are already 4 relays available on the KT-400. 
Make sure to check the relays number assignments to prevent 
redundancy unless it has been planned on purpose. 
2. Specifications 
• 
Maximum Current draw: up to 750 mA per module 
• 
Connects to the KT-400 via the 6-pin SPI connector 
• 
16 outputs low current module, 5 to 24 VDC, 4 to 750 mA 
• 
Can be used for elevator access control or general output 
• 
Can be mixed with output module KT-MOD-REL8 in the 
same SPI group 
3. 
Installing the KT-MOD-OUT16 
3.1. Unpacking 
The KT-MOD-OUT16 package includes the following parts: 
• 
One (1) KT-MOD-OUT16 module, 14 cm x 8 cm (5.7 in x 
3.25 in) 
• 
One (1) SPI cable with 1 SPI connector, 41 cm (16 in) 
• 
Four (4) plastic standoffs 
• 
Two (2) installation sheets, English and French 
 
3.2. Mounting 
The KT-MOD-OUT16 can be installed inside a compatible cabinet 
(KT-MOD-CAB or KT-400) or mounted in a dry and secure 
location at less than 1 m (3 ft) from the KT-400. 
Perform the following steps to mount the unit: 
1.  Press the four (4) plastic standoffs through the mounting 
holes of the cabinet,  
2.  Secure the cabinet to the wall in the desired location. Use 
appropriate wall anchors when securing the cabinet to 
drywall, plaster, concrete, brick or other surfaces, 
3.  Press the module into the plastic standoffs to secure the 
module to the cabinet. 
Once the unit is mounted, wiring may be started. 
3.3. Installation and Wiring 
Before beginning to wire the unit, ensure that all power (AC 
transformer and battery) is disconnected from the KT-400. 
Perform the following steps to complete wiring: 
1.  Connect the 6-pin SPI connector to: 
 
the KT-400 SPI port, or 
 
the SPI OUT of the previous output module (KT-MOD-
REL8 and KT-MOD-OUT16 only), or 
 
the SPI EXP of the 1st input module KT-MOD-INP16 
connected to the KT-400 SPI port. 
2.  Connect the six SPI wires (blue (BLU), white (WHT), green 
(GRN), yellow (YEL), black (BLK) and red (RED)) to the SPI 
IN (TB1) terminals. 
3.  Connect the 6-pin SPI connector from the SPI OUT to the 
next output module (KT-MOD-REL8 and KT-MOD-OUT16 
only). 
4.  Complete all output wiring.