Honeywell HSVR-04 Manuel D’Utilisation

Page de 161
Installation and Connections 
 
22 
Please connect the NC port of the alarm sensor to the DVR alarm input 
(ALARM) 
Use the same ground with that of DVR if you use external power for the 
alarm device. 
Note 
Only indoor devices are recommended for being connected 
to HSVR-04 / HSVR-16 alarm inputs. 
 
Figure 3-2 Sample of Alarm Input (Normal Close Type) 
 
Alarm Output Port 
  Three ways to relay alarm output (NO contact). External power supply 
is needed for external alarm device. 
  To avoid overloading, please read the following relay parameters sheet 
carefully. 
 
Relay Specification: 
Model JRC-27F 
Material of the touch  
Silver  
Rated switch capacity  
30VDC 2A, 125VAC 1A  
Maximum switch power  
125VA 160W  
Maximum switch voltage  
250VAC, 220VDC  
Rating (Resistance 
Load)  
Maximum switch currency  
1A