Reference Manual
00809-0100-4027, Rev AA
December 2005
Rosemount 4500
3-8
BASIC SETUP
Set Process Variable 
Units
The PV Unit command sets the process variable units to allow you to monitor 
your process using the appropriate units of measure. 
HART Communicator
Enter the fast key sequence for “Set Process Variable Units.” Select from the 
following engineering units:
AMS 
Right click on the device and select “Configuration Properties” from the menu. 
In the Basic Setup tab, use “Unit” drop down menu to select units.
Rerange
The Range Values command sets the 4 and 20 mA points (lower and upper 
range values). In practice, you may reset the transmitter range values as 
often as necessary to reflect changing process conditions. Changing the 
lower or upper range point results in similar changes to the span.
NOTE
Transmitters are shipped from Rosemount Inc. fully calibrated per request or 
to the factory default of full scale (span = upper range limit.)
Use one of the methods below to rerange the transmitter. Each method is 
unique; examine all options closely before deciding which method works best 
for your process.
Rerange with a HART Communicator only.
Rerange with a pressure input source and a HART Communicator.
Rerange with a pressure input source and the local zero and span 
buttons (option D1).
Rerange with AMS only.
Rerange with a pressure input source and AMS.
NOTE
If the transmitter security switch is ON, adjustments to the zero and span 
cannot be made. Refer to “Set Switches” on page 2-5 for security information.
Fast Keys
1, 3, 2
inH
2
O
bar
torr
inHg
mbar
atm
ftH
2
O
g/cm
2
MPa
mmH
2
O
kg/cm
2
inH
2
O at 4 °C
mmHg
Pa
mmH
2
O at 4 °C
psi
kPa