Routine Starting Procedure
After  periods  of  routine  shutdown,  the  following  restarting  procedure 
should be followed:
• Start the circulating water pump(s). Increase the flow of circulating water 
gradually to design water rate to avoid surges or water hammer which 
could damage the distribution piping.
 
Circulating cold water over a tower in freezing weather will cause ice 
to form, which may cause damage to the fill system. Water should be 
bypassed directly to the cold water basin until the heat load causes 
its temperature to rise above 0°F (1°C), at which time it may be 
directed over the tower. Also, towers must not be operated with 
reduced water rate and/or no heat load during freezing weather. If 
a bypass is used, do not modulate.
• Start the fan(s). On multi-cell towers, only as many fans should be started 
as  are  needed  to  produce  the  desired  cold  water  temperature.  If  the 
tower is equipped with two-speed motors, fans may be progressively 
started at half speed, increasing to full speed as necessary to maintain 
the  desired  cold  water  temperature.  (See 
Temperature  Control  and 
Energy Management on pages 13 and 14.)
 
 Caution