Sterling A0552321 Manuale Utente

Pagina di 36
Pump Tanks 
Chapter 3: Installation 
13 of 36 
 
 
Figure 1: Pipe Sizing Guide 
Pipe Sizing Guide 
Pipe Size 
Flow-Steel Pipe 
Flow-PVC Pipe 
1/2 2  2 
3/4 5  5 
1 10 10 
1 1/4 
20 
20 
1 1/2 
30 
30 
2 50 55 
2 1/2 
100 
100 
3 160 
160 
4 320 
320 
6 900 
1000 
8 2000 
2100 
10 3500 
3700 
12 5000 
5800 
Based on 10’ head loss/100’ of pipe (new pipe) — open piping systems. A safety factor of 15 
to 20% should be added based on local conditions.