Ensure that minimum clearances shown in Figures 4 through 7 are 
maintained. Left and right clearances are determined when facing the 
front of the firebox.  
Follow these instructions carefully to ensure safe installation. Failure to 
follow these requirements may create a fire hazard.
1.   Sidewall clearances:  The clearance from the inside of the appliance 
to any combustible wall should not be less than 6". See Figure 4.
2.   Ceiling clearance:  The ceiling must be at least 42” from the top of 
the firebox opening. See Figure 4.
3.  
Back wall clearance: The appliance may be placed against a com-
bustible back wall.
    
Figure 4 - Clearance and Height 
Requirements 
4.  
Floor  clearance:  This inner chamber firebox floor must be installed at least 1" above any combustible flooring mate-
rial, such as carpeting or asphalt tile, which is closer than 14" to the base of the firebox. See Figure 5. 
  Or
    The inner chamber firebox floor may be installed nearer to the floor if a minimum of 14" of noncombustible material 
such as slate or marble is installed between the base of the firebox and the combustible flooring. See Figure 6. 
Figure 5 - Minimum Clearance above 
Combustible Flooring 
Figure 6 - Minimum Clearance above Combustible 
Flooring with Non-Combustible Material Installed at 
Base of Fireplace 
14" Minimum
CLEARANCES 
AND
 HEIGHT REQUIREMENTS
Combustible 
Material 
1" minimum for 
LCUF32 and 36
Can be less than 1" 
for LCUF32 and 36
Non-Combustible 
Material