Air Handling Unit Limitations
Model
Power Supply Voltage
Voltage Variation
Supply Air Range CFM
Entering Air Temperature Degrees °F
Cooling
DB/WB
Heating DB
1
1
Heating Min/Max temperatures apply to steam and hot water coils. NOTE: Do not apply steam to hot water coils.
Min.
Max.
Min.
Max.
Min.
Max.
Min.
Max.
NH-07
208/230-3-60
187
253
2,250
3,750
65/57
90/77
40
80
460-3-60
414
506
2,250
3,750
65/57
90/77
40
80
575-3-60
540
630
2,250
3,750
65/57
90/77
40
80
NH-10
208/230-3-60
187
253
3,000
5,000
65/57
90/77
40
80
460-3-60
414
506
3,000
5,000
65/57
90/77
40
80
575-3-60
540
630
3,000
5,000
65/57
90/77
40
80
NJ-10
208/230-3-60
187
253
3,000
5,000
65/57
90/77
40
80
460-3-60
414
506
3,000
5,000
65/57
90/77
40
80
575-3-60
540
630
3,000
5,000
65/57
90/77
40
80
NH-15
208/230-3-60
187
253
4,500
7,500
65/57
90/77
40
80
460-3-60
414
506
4,500
7,500
65/57
90/77
40
80
575-3-60
540
630
4,500
7,500
65/57
90/77
40
80
NJ-15
208/230-3-60
187
253
4,500
7,500
65/57
90/77
40
80
460-3-60
414
506
4,500
7,500
65/57
90/77
40
80
575-3-60
540
630
4,500
7,500
65/57
90/77
40
80
NH-20
208/230-3-60
187
253
6,000
10,000
65/57
90/77
40
80
460-3-60
414
506
6,000
10,000
65/57
90/77
40
80
575-3-60
540
630
6,000
10,000
65/57
90/77
40
80
NJ-20
208/230-3-60
187
253
6,000
10,000
65/57
90/77
40
80
460-3-60
414
506
6,000
10,000
65/57
90/77
40
80
575-3-60
540
630
6,000
10,000
65/57
90/77
40
80