Power Wiring
Check the available power and the unit nameplate for correct 
voltage. Run the necessary number of properly sized wires to 
the unit. Provide a disconnect switch (if not included with the 
unit) and fusing as required (Factory disconnect is a fused 
disconnect /breaker). Route the conduit through the large 
knockout located near the electrical box. See Table 5 for 
Electrical Data.
The disconnect switch may be bolted to the side of the unit but 
not to any of the removable panels; which would interfere with 
access to the unit. Make sure that no refrigerant lines will be 
punctured when mounting the disconnect switch, and note that 
it must be suitable for outdoor installation.
Control Wiring
Route the necessary low voltage control wires from the 
Simplicity™ control board to the thermostat and also between 
the terminal blocks inside the heat pump and evaporator control 
boxes. Refer to Figures thru 6 for field wiring diagrams.
Compressors
The scroll compressors used in this product are specifically 
designed to operate with R-410A Refrigerant and cannot be 
interchanged.
The compressor also uses a polyolester (POE oil), Mobil 3MA 
POE. This oil is extremely hydroscopic, meaning it absorbs 
water readily. POE oil can absorb 15 times as much water as 
other oils designed for HCFC and CFC refrigerants. Take all 
necessary precautions to avoid exposure of the oil to the 
atmosphere.
POE (polyolester) compressor lubricants are known to cause 
long term damage to some synthetic roofing materials.
Procedures which risk oil leakage include, but are not limited to, 
compressor replacement, repairing refrigerant leaks, replacing 
refrigerant components such as filter drier, pressure switch, 
metering device or coil.
The unit is shipped with compressor mounting bolts which are 
factory adjusted and ready for operation.
Phasing
Three-phase, scroll compressors operate in only one direction. 
If the scroll is drawing low amperage, has similar suction and 
discharge pressures, or is producing a high noise level, the 
scroll is misphased. Change the incoming line connection 
phasing to obtain the proper rotation.
All power and control wiring must be in accordance 
with National and Local electrical codes.
This system uses R-410A Refrigerant which operates at 
higher pressures than R-22. No other refrigerant may be 
used in this system.
Do not leave the system open to the atmosphere. Unit 
damage could occur due to moisture being absorbed by 
the POE oil in the system. This type of oil is highly 
susceptible to moisture absorption
Exposure, even if immediately cleaned up, may cause 
embrittlement (leading to cracking) to occur in one year 
or more. When performing any service that may risk 
exposure of compressor oil to the roof, take precautions 
to protect roofing.
Do not loosen compressor mounting bolts.
Scroll compressors require proper rotation to operate 
properly. Failure to check and correct rotation may result 
in property damage.