Sanyo Quick Connect Guide
Indoor Unit Model
Outdoor Unit Model
SPW 4:1 Inverter 165 H
Standard PAC SPW CR 604 GVH56B / GVH8B
PIPING
SUCTION
5/8" to joint 1/2" from joint to indoor
LIQUID
3/8" to joint 1/4" from joint to indoor
GAS PRE CHARGE LENGTH
30m
ADDITIONAL CHARGE
3/8" = 40 g/m & 1/4" = 20 g/m
MAXIMUM PIPING LENGTH
50m
INTERCONNECTING WIRING
SUGGESTED CABLE SIZE
0.75 mm (Shielded)
NUMBER OF CORES
2
POWER SUPPLY WIRING
INDOOR UNIT POWER SUPPLY
5a Single Phase
OUTDOOR UNIT POWER SUPPLY
GVH56B 40a Single Phase - GVH8B 16a Three Phase
REMOTE CONTROLLER WIRING
SUGGESTED CABLE SIZE
0.75 mm (Shielded)
NUMBER OF CORES
2