Emerson 3000/ITR Manuale Utente

Pagina di 72
Troubleshooting
56
8.0
T
ROUBLESHOOTING
Use this section to assist in troubleshooting your unit. Also refer to 6.0 - Alarm Descriptions. Sug-
gestions are grouped by product function for convenience.
NOTICE
Risk of improper control connection. Can cause equipment damage.
When using jumpers for troubleshooting, always remove jumpers when maintenance is 
complete. Jumpers left connected could override controls and cause equipment damage.
!
WARNING
Risk of electric shock. Can cause injury or death.
The Liebert iCOM microprocessor does not isolate power from the unit, even in the “Unit Off” 
mode. Some internal components require and receive power even during the “Unit Off” mode 
of Liebert iCOM control.
The only way to ensure that there is NO voltage inside the unit is to install and open a remote 
disconnect switch. Refer to unit electrical schematic.
Only properly trained and qualified personnel should service these units. Lethal voltage is 
present in some circuits. Use caution when troubleshooting with power On. Disconnect and 
lock out power before replacing components.
!
WARNING
Risk of explosive discharge from high-pressure refrigerant. Can cause injury or death.
This unit contains fluids and gases under high pressure. Relieve pressure before working with 
piping.
Table 12
Blower troubleshooting
Symptom
Possible Cause
Check or Remedy
Blower will not 
start
No main power
Check L1, L2 and L3 for rated voltage.
Blown fuse or tripped circuit breaker (CB)
Check fuses or CBs to main fan.
Overloads tripped
Push reset button on main fan overload. Check amp draw.
No output voltage from transformer
Check for 24 VAC between P24-2 and P24-1. If no 
voltage, check primary voltage.
Control fuse blown or circuit breaker tripped
Check for 24 VAC between P4-4 and E1. If no voltage, 
check for short. Replace fuse or reset circuit breaker.
Table 13
Chilled water troubleshooting
Symptom
Possible Cause
Check or Remedy
Chilled water or hot 
water/steam valve 
not opening
Motor operates but valve 
won’t open
Check linkage for adjustment and be sure that it is tight on the valve.
Modulating Motors
No 24 VAC power to motor
Check linkage for adjustment and be sure that it is tight on the valve.
No signal from control
Check DC voltage on printed circuit board in motor. Terminal No. 1 is 
grounded and No. 3 is positive. DC voltage should vary from 0.8 to 
2.0 VDC or above as temperature control is varied below room 
temperature on cooling valve or above room temperature on heating 
valve.
Motor not working
Remove wires on Terminal No. 1 and No. 3 from the motor (do not 
short). With 24 VAC power from TR to TR jumper terminal 1 and 2 on 
motor to drive open. Remove jumper to drive closed, if motor fails to 
work, replace it.
Actuator Motors
No 24 VAC power to motor
Check for 24 VAC between P22-3 and P22-5 (open), or P22-1 and 
P22-5 (closed).