Troubleshooting
59
Table 15
Dehumidification troubleshooting
Symptom
Possible Cause
Check or Remedy
No dehumidification
Control not calling for 
dehumidification
Check monitor status.
Compressor contactor not pulling in
Compressor won't run; fuse blown or 
CB tripped
and contacts. Check line voltage
Table 16
Glycol pump troubleshooting
Symptom
Possible Cause
Check or Remedy
Suddenly stops pumping
Clogged strainer or impeller
Clean out debris.
Suddenly slow pumping
Clogged impeller, diffuser, or line
Clean out debris and use strainer.
Excessive leakage around the pump 
shaft while operating
Worn seal or packing
Replace seal or packing.
Performance poor
Worn impeller or seal
Replace with new impeller or seal.
Suction lift too high
Relocate pump closer to supply.
Motor not up to speed; low voltage
Larger lead wires may be required. Check 
for proper line voltage (±10%).
Worn bearings
Replace pump
Noisy operation
Worn motor bearings
Replace pump
Low discharge head
Throttle discharge-improve suction 
conditions.
Debris lodged in impeller
Remove cover and clean out.
Cavitating pumps
Adjust system pressures.
Table 17
Infrared humidifier troubleshooting
Symptom
Possible Cause
Check or Remedy
No humidification
Humidifier pan not filling
Check water supply.
Check fill valve operation
Check drain stand pipe adjustment
Check for clogged waterline
Control not calling for humidity
Check monitor status
Humidity contact not pulling in
Check visually. If contact is made, check 
line voltage after contactor and fuses or 
CBs.
Check for open humidifier safety stat. 
Jumper between terminals P35-6 and 
P35-15. If contactor pulls in, replace 
safety. Remove jumper.
Humidifier bulb burned out
Replace bulb. Loosen lead on old bulb. 
Trim excess lead length on new bulb to 
avoid shorts.