ELECTRICAL WIRING 
Follow  local  electrical  codes  when  making  electrical 
connections. Units are completely factory wired for normal 
supply  voltages  (ie.208-230,  460,  575/3phase/60Hz) 
Confirm unit specifications by checking unit data plate. 
The factory wiring terminates in two boxes, one in each 
section  of  the  unit. The  electrical  control  boxes  are 
located  behind  outer  access  panels.  Each  electrical 
compartment has its own control cover. 
Provide individual power disconnects for each unit, or 
each section in the case of split applications. Install a 
secure  ground  to  both  evaporator  and  condenser.  If 
canvas joiners are used on ductwork, install a ground 
wire to the ductwork as well. Unit requires installer to 
provide  a  24volt  thermostat  with  appropriate  heating 
and cooling stages as needed. The condenser section 
electrical cover is installed with wiring diagrams on the 
inner access door, which must be opened to read the 
diagrams. 
Disconnect  and  lock  out  power  when 
servicing unit. Unit may start automati-
cally if power is not disconnected. Fail-
ure to do so may result in personal injury 
or death due to electrical shock. 
PACKAGED UNIT 
If unit is to be installed as a complete integral unit, the 
thermostat (low voltage) wiring is to be brought through 
connection  “A”,  while  power  wiring  will  be  brought 
through connection “C”). Make sure you check the unit 
data plate for full specifications as previously mentioned 
(i.e. minimum circuit ampacity and fuse size). 
SPLIT SYSTEM 
If the unit is a split system application (condenser sec-
tion remote from evaporator section), the following wir-
ing instructions are applicable. The thermostat wiring 
is  brought  through  connection  “A”  on  the  evaporator 
section, and is then interconnected via connection “B” 
on the condenser section. The power wiring is brought 
through “C” on the condenser section. The power feed 
to the evaporator is run through “D” on the evaporator 
section. 
IMPORTANT: All  wiring  must  comply 
with applicable local and national codes 
(NEC). Type and location of disconnect 
switches must comply with all applicable 
codes.
 
For low voltage wiring, 18 gauge wire may be used for 
up to 50 feet lengths. Low voltage runs up to 125 feet 
require 16-gauge wire.